Audio/Technical Specifications

Switch mode, Class D amplifier (40 Watts)

Speaker Outputs

25V or 70.7V power limited

Frequency Response

Voice:

 275 Hz – 6.5 kHz 

BGM:

 100 Hz - 15 kHz 

Meets UL Voice Evacuation 

Requirements of 800 - 2800 Hz

Signal to Noise Ratio

better than 65 dB

Dynamic Range

better than 65 dB 

Total Harmonic Distortion less than 2%
Stand by Current Draw

140 mA

Alarm Current Draw

4.7 amps

Inputs – Audio and Activation

Priority Ordered Inputs  

Priority 

Level

Type of Input

On Board Microphone

Push to Talk (PTT) Microphone

Auxiliary

2

Remote Microphone or Remote Microphone Expander

Digital Message Input 1

3

Contact Closure activation

Digital Message Input 2

4

Digital Message Input 3

5

Digital Message Input 4

6

Digital Message Input 5

7

Digital Message Input 6

8

Digital Message Input 7

9

Digital Message Input 8

10

Night Ringer Input

11

Contact Closure input

Telephone Paging Input

12

Page port input

Background Music Input

13

Line Level Input, 600 ohm, input voltage must be less then 2.5 V peak to peak, or .3 volts RMS

Compatible Wheelock Products

All Wheelock Speaker/Strobes
All Wheelock Strobes
All Wheelock Speakers 
All Cluster Speakers 
Wheelock Strobe Power Supply 

Live & Pre-recorded Message Announcement

•  Supplied with 8 pre-recorded emergency messages 
•  Capable of in-field recording of all messages via 1/8” line level audio input  
  jack
•  Preset audio levels for emergency messaging (prerecorded and live mic) -  
  system reverts back to a pre set level regardless of the volume set for BGM  
  or general paging
•  On board Push-to-Talk Microphone
•  Telephone paging input, disconnects BGM when in use
•   Auxiliary input for Remote Microphone connection

Installation/Maintenance

•  Multiple trouble LED indicators for quick system diagnostics
•  Fully supervised circuitry always in effect – even during BGM and 

general paging (via patent pending technology)

•  Removable quick connect/disconnect terminals for ease of wiring, 

accepts #12 to #22 AWG

•  Power limited circuitry with Class “B” or Class “A” wiring.  Class “A”
    only with use of Audio Splitter
•  Surge protected circuitry

Power Supply & Batteries

•  24 VDC, 33AH Max rechargeable battery back-up power circuitry 
built-in
•  Batteries can be housed in the enclosure (Up to two (BAT-1212),  
  12 volt, 12 ampere hour batteries can fit in the enclosure. 
  Actual battery size required will depend on speaker and/or strobe  

Benefits and Advantages of the Multi-Function SAFEPATH4

•  One System Multi-Function Facility Communications System
•  Background Music (BGM) system, with patent pending supervision during BGM  
  operation
•  Supervised Emergency/Fire Voice Evacuation System
•  Interfaces with telephone system for general paging requirements
•  Built in power for visual notification appliances e.g., Strobes
•  Expandable for larger system requirements (with optional equipment)

Audio Processing

•  Volume and tone controls for general paging and BGM
•  Connectability of optional speaker splitter modules 
•  Dual-tone tone generator with: Code 3 Tone and Slow Whoop for alerting  
  of system trouble
•  Night ringer/security alerting capability
•  Audio power can be expanded by connecting to optional audio power  
  boosters 

-SPB-80/4  80 Watt Supervised  Audio Power Booster with 4 Amp 
 of Synchronized Strobe Power 

 

-SPB-160  160 Watt Supervised Audio Power Booster

 

-SPB-320  320 Watt Supervised Audio Power Booster 

3

Mechanical

Dimensions

 21” H x 16” W x 6” D 
(wall mount)

Weight

36 lbs.
(without batteries)

Finish

Red or black exterior 
enclosure

Door Lock

Wheelock Key-lock

Summary of Contents for SAFEPATH SP4Z-A-B

Page 1: ... B Speaker Audio Splitter 5 SAFEPATH 4 Audio Boosters 6 7 System Diagram 8 9 SAFEPATH 4 Addressable Paging Splitter and Telephone Zone Controller 10 SAFEPATH 4 Supervised Volume Control and Remote Microphone 11 Remote Microphone Expansion Module 12 Description Page SP40S SPRM SP4Z A B SP SVC SP4 TZC 151 92 E S5361 6911 0785 157 SPB 80 4 SPB 160 SPB 320 SP4 APS ...

Page 2: ... pagers for private alerting of emergency trouble conditions System Activation Contact closure message activation Approvals Compliance Approvals UL Standard 864 9th edition UL Standard 1711 California State Fire Marshal CSFM New York City MEA FCC Part 15 OSHA 1910 165 and ADA Compliant 3 Year Warranty Made in the USA Background Music Capable of broadcasting from a supplied BGM source Unique superv...

Page 3: ...or Remote Microphone connection Installation Maintenance Multiple trouble LED indicators for quick system diagnostics Fully supervised circuitry always in effect even during BGM and general paging via patent pending technology Removable quick connect disconnect terminals for ease of wiring accepts 12 to 22 AWG Power limited circuitry with Class B or Class A wiring Class A only with use of Audio Sp...

Page 4: ...tention please A fire emergency has been reported in the building While this is being verified please leave the building by the nearest exit Do not use the elevators 2 Fire do not use elevators Female Three 3 rounds of code 3 horn followed by May I have your attention please A fire emergency has been reported in the building While this is being verified please leave the building by the nearest exit Do...

Page 5: ...ither 25V or 70 7V RMS Mounts inside the enclosure of the SP40S SP40 2 or Audio Boosters Power and Trouble LED s Individual zone short and open LED indication Capable of detecting wiring faults Removable wiring terminals for quick connect disconnect accepting 12 22 AWG All output circuitry is Power Limited Space provided to allow for naming of the zones Powered by 24VDC supplied by the either the ...

Page 6: ... achieved Additional strobe power can be obtained via a combination of SPB 80 4 or Wheelock Power Supplies Chargers Power Supply Batteries Fully supervised patent pending circuitry always in effect even during BGM Power limited circuitry Class D amplifiers Internal battery charger and power supply Required batteries fit inside the enclosure sold separately SPB 320 requires four 12 VDC 12 AH batterie...

Page 7: ...150 160 Watt Supervised Audio Power Booster Two 80 watt circuits 220 VAC input black enclosure SPB 80 4 8988 80 Watt Supervised Audio Power Booster with 4 Amps of Supervised and Synchronized Strobe Power Two 2 Amp circuits red enclosure SPB 80 4 B 9931 80 Watt Supervised Audio Power Booster with 4 Amps of Supervised and Synchronized Strobe Power Two 2 Amp circuits black enclosure SPB 80 4E 6147 80...

Page 8: ...elock Strobe Power Supplies SP40S Supervised Multi Function Communication System SPB 80 4 80 Watt Audio Booster 4 Amps of Strobe Power SPB 160 160 Watt Audio Booster SPB 320 320 Watt Audio Booster SPRM Remote Microphone SP4 RMX Remote Microphone Expansion Module SP4 TZC Telephone Zone Controller SP4 APS Addressable Paging Splitter SP4Z A B Speaker Splitter SP4 SVC Supervised Volume Control Strobe ...

Page 9: ... SPB 160 SP4Z A B SP4 APS SPB 320 SP4 APS SP4Z A B SPB 160 SP4 APS SP4 APS Wheelock Strobe Power Supply Wheelock Strobe Power Supply SP4 APS SP4 APS SPB 320 SP4 APS SP4 APS SP4 APS SP4Z A B SPB 160 SP4 APS SP4 APS V V V ...

Page 10: ...ing Splitter SP4 TZC Telephone Zone Controller Class B 4 zones per splitter Up to 68 individual zones 17 splitters 17 fixed zones groups of 4 9 logical zones Class A 2 zones per splitter Up to 34 individual zones 17 splitters 17 fixed zones groups of 2 9 logical zones SP4 TZC Telephone Zone Controller Connects to the SP40S or SP40 2 Auto programmable Custom user programmable for logical zones All ca...

Page 11: ...rent Standby 26mA Alarm 38mA Audio output level 1 05V RMS 6 wire connection to the SP40S SP40 2 or SP4 RMX Mounting plate is red and measures 8 3 4 x 5 fits into a 4 gang back box All output circuitry is Power Limited SAFEPATH 4 Remote Microphone 11 Applications Features Model Order Code Description SP SVC 9926 Supervised Volume Control for use with the SAFEPATH 4 system Ordering Information SAFEPA...

Page 12: ...en the SP4 RMX is connected to the SP40S or SP40 2 the entire system benefits from the additional microphone capability Can be connected to Audio Boosters for general non alarm paging with use of SPRM GP UL Standard 864 listed OSHA 1910 165 ADA and UFC compliant Multiple on board diagnostics with 3 status conditions standby alarm and trouble Operates on 24 VDC supplied by the SP40S SP40 2 SPB 80 4 ...

Page 13: ...its SPB 160 8989 160 Watt Supervised Audio Power Booster Two 80 watt circuits red enclosure SPB 160 B 9930 160 Watt Supervised Audio Power Booster Two 80 watt circuits black enclosure SPB 80 4 8988 80 Watt Supervised Audio Power Booster with 4 Amps of Supervised and Synchronized Strobe Power Two 2 Amp circuits red enclosure SPB 80 4 B 9931 80 Watt Supervised Audio Power Booster with 4 Amps of Supe...

Page 14: ...shall be made in the USA Approvals for the system shall include UL Standard 864 9th edition UL Standard 1711 FCC part 15 California State Fire Marshal CSFM and New York City MEA The system shall be OSHA 1910 165 and ADA compliant 3 Year Warranty SAFEPATH 4 Audio Boosters The Wheelock SPB 320 SPB 160 and SPB 80 4 Audio Boosters shall be NFPA compliant supervised audio and supervised 24VDC synchroni...

Page 15: ...odules and shall be capable of addressing all zones at once All Call a maximum of 68 separate zones 17 fixed zone groups and 9 programmed logical zone groups This shall be accomplished using two digit DTMF tones from a page port an unused CO port or a stand alone telephone with a loop start circuit Also the SP4 TZC shall be able to select zones for background music The SP4 TZC has the following inp...

Page 16: ...o the SP40S or SP40 2 and shall have the capability of providing the SP40S or SP40 2 with up to six system wide All Call Remote Microphone SPRM modules The SP4 RMX can be programmed to provide either priority override for each SPRM module input or First In First Out First In First Out allows the active SPRM to complete its communication before another SPRM can be used All output circuitry shall be...

Reviews: