INS #

IB505067EN 

AtLite

Installation Instructions for the AtLite ATLEM1002HR16SD/ATLEM2002HR14SD/ 

ATLEM3002HR10SD Emergency Light

 WARNING 

Risk of Fire/Electric Shock

If not qualified, consult an electrician.

 WARNING 

Risk of Electric Shock

Disconnect power at fuse or circuit breaker before 

installing or servicing.

IMPORTANT SAFEGUARDS

WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY 
PRECAUTIONS SHOULD ALWAYS BE OBSERVED INCLUDING 
THE FOLLOWING.

READ AND FOLLOW ALL

SAFETY INSTRUCTIONS

1. Do not use outdoors.

2. Do not use in hazardous locations, or near gas or electric

heaters.

3. Do not let power supply cords touch hot surfaces.

4. Do not use this equipment for other than the intended use.

5. Installation is to be performed only by qualified personnel.

6. Install in accordance with National Electric Code and local

regulatory agency requirements.

7.  The use of accessory equipment not recommended by the

manufacturer may cause an unsafe condition.

8. Equipment should be mounted in locations and at heights

where it will not readily be subjected to tampering by
unauthorized personnel.

SAVE THESE

INSTRUCTIONS

MAX MOUNTING HEIGHT: 27.6 ft.

INSTALLATION

1. De-energize the circuit at the junction box (J-box) where

the emergency light is to be installed.

2. Open the emergency light by removing the sheet metal

screw from the bottom of the fixture, then tipping the
cover up off of the backplate (See Fig. 1).

3. To mount to a junction box - Knock out the appropriate

mounting pattern and the wire pass hole in the backplate
to fit the J-box being used.

4. To mount using conduit, mount the backplate to the wall

in the desired location. Attach a conduit hub to whichever
of the three conduit mount points on the backplate is most
convenient. (see Fig. 2) Remove the corresponding U shaped
cover from the housing by wiggling it back and forth until it
breaks free. (see Fig. 3)

NOTE:

 A fourth conduit mount location is available on the 

bottom surface of the housing, but it can only be used with 
flex conduit. 

5. Once the backplate is secured, the housing can be held in

place during installation using the EZ Hang feature. (Fig. 2)

6. Connect incoming ground to the green ground wire.
7. Connect the incoming wires to the fixture’s power supply

wires using the wire nuts provided.  Connect the white
wire to neutral.  Connect the black wire to the hot
lead.  The ATLEM1002HR16SD / ATLEM2002HR14SD /
ATLEM3002HR10SD uses a universal input power supply that
will accept from 120-277VAC (see Schematic).

8. Determine the incoming voltage, and select the appropriate

jumper for the brownout circuit (see Schematic). Because
of the universal input of the ATLEM1002HR16SD /
ATLEM2002HR14SD / ATLEM3002HR10SD, the battery
charger will continue to function if voltage sags, even if
the normal power lights in the area fail.  Selecting the
appropriate incoming voltage sets the voltage threshold for
the brownout circuit, so that the emergency lights will come
on if voltage sags.  The fixture ships with the circuit set to
120V.

9. LED remotes can be connected using the violet (+) and yellow

(-) wires. See schematic.

10. Replace the housing onto the backplate. Secure the backplate

with the sheet metal screw.

11. Remove EZ Key to connect the battery. Battery will not

charge with the EZ Key in place.

12.Energize AC supply. The test button should illuminate, and

the LED heads will illuminate briefly when the test button is
pushed.

13.Adjust remote heads (not included) as needed.
14.Allow 24 hours for batteries to charge.
15.If the fixture is to be powered down for an extended period

after initial installation, replace the EZ Key. This will prevent
the battery from discharging when AC power is removed.
However, it will also prevent the battery from charging when
AC power is restored, so it must be removed once the unit is
ready for regular operation.