Installation Instructions for the AtLite ATLEM Emergency Light
ACTIVATING TIME DELAY
The ATLEM1002HR16SD / ATLEM2002HR14SD /
ATLEM3002HR10SD series has an integrated time delay circuit
that allows them to remain in emergency mode 15 minutes
after power is restored. To activate the time delay, remove the
jumper on the circuit board labeled TDI/J4.
SETTING BROWN OUT CIRCUIT
Because of the universal input of the ATLEM1002HR16SD /
ATLEM2002HR14SD / ATLEM3002HR10SD, the battery charger
will continue to function if voltage sags, even if the normal
power lights in the area fail. Selecting the appropriate incoming
voltage sets the voltage threshold for the brownout circuit,
so that the emergency lights will come on if voltage sags.
The fixture ships with the circuit set to 120V. Determine the
incoming voltage, and select the appropriate jumper for the
brownout circuit (see Schematic).
OPERATION
The AtLite Eagle Eye Self Diagnostics is continuously
monitoring your emergency fixture, and will signal any failure
through the 3 color indicator LED.
Initial Operation
When the unit is first powered up, it will go into a 24 hour fast
charge, indicated by the indicator LED pulsing green. Once the
unit has fully charged, it will perform a self calibration, after
which the LED will change to steady green, indicating the unit
is fully charged and float charging the battery to maintain
readiness.
Automatic Testing
The unit will perform a battery capacity, lamp/LED, and charge
circuit test every 30 days for 30 seconds. During this time, the
indicator LED will change to a steady yellow. It will perform a
full battery capacity (90 minute) test once per year. During this
time, the indicator LED will change to a blinking yellow.
Manual Testing
• 10 Second “Installation” test – Press and release the test
button once during fast charge (blinking green) to initiate a 10
second quick test. The sign will switch to emergency mode for
10 seconds allowing the installer to verify proper installation of
the unit, and the LED indicator will turn solid yellow.
• 30 Second Test -Press and release the test button once during
float charge (steady green). The indicator LED will turn steady
yellow to indicate the unit is performing a 30 second test of the
batteries and lamps/LEDs.
• 90 Minute Test -Press and release the test button a second
time during a 30 second test (steady yellow) to change to a
90 minute test. During this test, the LED indicator will change
to blinking yellow, and the circuit will perform a full battery
capacity, charge circuit, and LED test.
• Canceling Test – Press and release the test button during
the 90 minute test (flashing yellow) to return the fixture to its
original state (fast charge or float charge).
Laser Testing
The ATLEM series is equipped with a Laser Test function, that
allows the unit to be manually tested without the need to
physically press the test button. Shining a laser pointer in the
hole marked “LASER TEST” on the bottom of the unit has the
same effect as a press and release of the test button.
Figure 2
Bottom conduit mount -
flex only
Conduit mount points
Figure 3
Gently wiggle the
U-shaped conduit
covers to break off.
Slide hooks
through slots
in housing for
temporary mount
when wiring.
Figure 1
Remove screw
and tip housing up
to open fixture.