Installation Instructions for the AtLite ATLEM Emergency Light

ACTIVATING TIME DELAY

The ATLEM1002HR16SD / ATLEM2002HR14SD / 
ATLEM3002HR10SD series has an integrated time delay circuit 
that allows them to remain in emergency mode 15 minutes 
after  power is restored. To activate the time delay, remove the 
jumper on the circuit board labeled TDI/J4.

SETTING BROWN OUT CIRCUIT

Because of the universal input of the ATLEM1002HR16SD / 
ATLEM2002HR14SD / ATLEM3002HR10SD, the battery charger 
will continue to function if voltage sags, even if the normal 
power lights in the area fail. Selecting the appropriate incoming 
voltage sets the voltage threshold for the brownout circuit, 
so that the emergency lights will come on if voltage sags. 
The fixture ships with the circuit set to 120V. Determine the 
incoming voltage, and select the appropriate jumper for the 
brownout circuit (see Schematic).

OPERATION

The AtLite Eagle Eye Self Diagnostics is continuously 
monitoring your emergency fixture, and will signal any failure 
through the 3 color indicator LED.

Initial Operation

 

When the unit is first powered up, it will go into a 24 hour fast 
charge, indicated by the indicator LED pulsing green. Once the 
unit has fully charged, it will perform a self calibration, after 
which the LED will change to steady green, indicating the unit 
is fully charged and float charging the battery to maintain  
readiness.

Automatic Testing 

The unit will perform a battery capacity, lamp/LED, and charge 
circuit test every 30 days for 30 seconds. During this time, the 
indicator LED will change to a steady yellow. It will perform a 
full battery capacity (90 minute) test once per year. During this 
time, the indicator LED will change to a blinking yellow.

Manual Testing

• 10 Second “Installation” test – Press and release the test
button once during fast charge (blinking green) to initiate a 10
second quick test. The sign will switch to emergency mode for
10 seconds allowing the installer to verify proper installation of
the unit, and the LED indicator will turn solid yellow.

• 30 Second Test -Press and release the test button once during
float charge (steady green). The indicator LED will turn steady
yellow to indicate the unit is performing a 30 second test of the
batteries and lamps/LEDs.

• 90 Minute Test -Press and release the test button a second

time during a 30 second test (steady yellow) to change to a
90 minute test. During this test, the LED indicator will change
to blinking yellow, and the circuit will perform a full battery
capacity, charge circuit, and LED test.

• Canceling Test – Press and release the test button during
the 90 minute test (flashing yellow) to return the fixture to its
original state (fast charge or float charge).

Laser Testing

The ATLEM series is equipped with a Laser Test function, that 
allows the unit to be manually tested without the need to 
physically press the test button. Shining a laser pointer in the 
hole marked “LASER TEST” on the bottom of the unit has the 
same effect as a press and release of the test button.

Figure 2

Bottom conduit mount -

flex only

Conduit mount points

Figure 3

Gently wiggle the 

U-shaped conduit

covers to break off.

Slide hooks 

through slots 

in housing for 

temporary mount 

when wiring.

Figure 1

Remove screw 

and tip housing up 

to open fixture.