CEAG Notlichtsysteme GmbH
13
Operating Instructions
Self contained luminaire Alu-Klick
71811...71821 (CG Line)
6
Installation
For the mounting and
operation of electrical
apparatus, the
respective national
safety regulations
(e.g. ElexV, equipment
safety law for
Germany) as well as
the general rules of
engineering will have
to be observed.
6.1 Mounting
Remove cover (see fig. 5,
page 4).
Take off lamp.
Introduce mains cable.
Mount enclosure with 2
screws and 2 dowels
through the fixing holes at
the ceiling or wall.
For pendulum set mounting
and chain suspension see
manual of accessory set!
Connect mains to terminals
L(U), L´(U), N(O) and PE
(function earth only) (for
71821 use separate PE).
L = unswitched permanent
connection
L`= switch on demand
Plug the faston plugs of the
battery cables to the contact
plugs on the conductor
board - red wire to +(plus),
blue wire to -(minus) (s. page
3, fig. 2).
Insert lamp.
Insert cover (fig. 1, page 3).
Optionally, every luminaire
can be operated with light
switching (switched
maintained light), in non-
maintained mode (without
jumper) or in maintained
mode (with jumper). (see
above)
Mains connection:
B u t t o n / L E D - f o i l -
connection
Changing button/LED or
printed circuit please see
marker 1 on the printed
circuit and on the printed
conductor.
6.2 CG Line Monitoring
Device
The self-contained lumi-
naires 71811 / 71821 CG
Line are prepared for
connection to the CEAG CG
Controller CG Line 400. An
individual, distinct identifi-
cation number (6 characters)
is assigned to every
luminaire in the CG Line
luminaire series.
This ID-number must be
transfered to the installation
plan for subsequent
configuration work. The
removable ID sticker in the
luminaire can be used for
this. Up to 100 luminaires
can be connected to a 2-core
bus cable and linked to the
CG Controller CG Line 400.
The CG-Controller can
monitor max. 4 bus cables
with 100 luminaires each.
The max. data line
length per strand is
0,5 mm² -
450 m
1,0 mm² -
900 m
1,5 mm² - 1300 m
Data per line:
Bus voltage
22,5 VDC
Max. voltage drop
13,0 VDC
Bus current
400 mA
Fig. 19
Fig. 20
non maintained
light
After mains return the
emergency operation will
stay for approx. 1 minute!
(delay on mains return)