CEAG Notlichtsysteme GmbH
14
Operating Instructions
Self contained luminaire Alu-Klick
71811...71821 (CG Line)
7
Servicing
Observe the relevant natio-
nal regulations which apply
to the maintenance,
servicing and check of
electrical apparatus!
8
Recycling
When a defective apparatus
is disposed of, the respective
national regulations on
waste disposal and recycling
will have to be observed.
Plastic parts have been
provided with respective
symbols.
6.3 Mounting accessories
fig. 22
An unscreened, 2-core cable
with free bus topology can
be used as a data cable.
Each of the luminaires
connected to the data bus
cable is automatically
recognised by the CG
controller. The CG Control-
ler can assign a short
address to the connected
luminaires, which can be
polled via the three LEDs on
the luminaire.
TEST
grün gelb rot
green yellow red
Fig. 21
The three LED´s on the
luminaire indicate the
following status:
-
no fault
-
luminaire in function test
-
luminaire in duration test
-
charging fault
-
function-test fault
-
duration-test fault
-
luminescent material
faulty
Accessory
wall bracket and
Pendulum Set
Pendulum Set
Pendulum Set Chain suspension
Wire guard
ceiling mounting set
0,5 m
1,0 m
1,5 m
order no.
400 71 351 011
400 71 350 412 400 71 350 414 400 71 350 416 400 71 351 158 400 71 348 370
71811
u
71811 CG Line
u
71821
u
u
u
u
u
71821 CG Line
u
u
u
u
u
In addition, the following can
be started and displayed
with the test button:
-
function test ON
-
duration test ON / OFF
-
duration test delayed
-
setting the emergency
light operating time with
subsequent identificati-
on of the luminaire short
address (when data bus
is connected and the CG
Controller has issued
short addresses).
The delayed duration test is
displayed if the luminaire is
not charged without
interruption for 24h or if an
duration test was started
within the 24h. (s. fig 23,
page 15)
For further details see the
operating manual of the CG
Controller CG Line 400, no.
400 71 860 016.
Autarchic Operation
After the initial installation /
mains connection the
luminaire starts the function
test weekly and a duration
test every three months also
without the CG Controller
CG Line.
The single pendulum is also available in a quadratic version with the following dimensions:
0,1m
400 71 351 497
0,5m
400 71 351 498
for ceiling mounting (similar to ceiling mounting set, fig. 6).