background image

Cooper Lighting and Safety Ltd, Wheatley Hall Road, Doncaster, South Yorkshire, DN2 4NB. UK.
T: +44 (0) 1302 303350 l F: +44 (0) 1302 303332 l E: techsupport@cooperfire.com l W: www.cooperfire.com

Intelligent Addressable Passive Repeater Panel - DF6000PR

Code

CF30000PR

Description 

Passive repeater panel

Standards

EN54 Pt4

Specification

Mains Input Voltage 

230V ac +10% / -15%

Operating Voltage

24V dc

System Indicators

Power on, fire, fault, test, disable and scroll 

System Controls

Silence alarms, evacuate and reset

Input Ports 

RS232 (for connection of programmer) 

Battery 

1 x 12V 3.2Ah

Standby Duration 

24 hours

Environmental

Operating Temperature 

0°C to +25°C

Humidity (Non Condensing) 

0 to 75% RH

Physical

Construction 

PC/ABS

Colour 

Light Grey

Dimensions (H x W x D) 

332mm x 270mm x 92mm

Weight 

3.6kg

Ingress Protection 

IP30

Compatibility

Suitable for use with 

Menvier intelligent addressable fire systems

Technical Specification

Installation

1. Wall mounted by means of 4 fixing screws.
2. Cable entry at top or back.
3. 12 top entry gland holes with push out blanking 

plugs.

4. 4 separate rear access cable entry facilities.
5. Local mains supply required.

System Functionality

1. Panel operates in either normal, supervisor or 

engineer mode.

2. Supervisor and engineer modes are accessed via 

4 digit pass codes.

3. Supervisor mode allows silence, evacuate and 

reset commands to be sent to host panel (loop 
connected) or to network (network connected).

4. Engineer mode enables password to be changed if

required and allows access to text download menu

5. When connected to network, all text is transmitted 

via network, changes to other network panels 
update automatically.

6. When connected to a detector 

loop, text for host is
downloaded to repeater and 
updated manually as required.

7. Zonal fire and fault indication is

by means of 2 x 40 character 
LCD display.

Device Overview

1. Panel can be connected to 

either the detection loop of a 
single panel or to a network as 
part of a networked system.

2. Supplied with integral power 

supply and standby battery.

Dimensions

W

H

D2

D1

1

2

3

4

5

SCROLL

MUTE

BUZZER

H (mm)

W (mm)

D1 (mm)

D2 (mm)

270

332

45

47

Code

Description

DF6000PR 

Intelligent addressable passive repeater panel, loop connected

DF6000PRNC 

Intelligent addressable passive repeater panel, network connected

Product Codes

Mains Supply

Network Link

Mains Supply

Mains Supply

Network Link

Loop Connected

Network Connected

Note:

In this configuration the repeater would give 
‘text’ information for the panel that is on the 
loop, but only address number for the other 
panel on the network.

Standard Connection

- +

SCREEN

- +

SCREEN

LOOP

OUT

LOOP

IN

SCREEN

Tx +

Tx -

Rs485

MIMIC

TEXT DOWNLOAD

cfs0018_UK_R1_menvier-data-sheets_Layout 1  04/08/2011  12:05  Page 62

Intelligent Security & Fire Ltd

Reviews: