49
S280-77-4
!
SAFETY
FOR LIFE
Clock
Security
Limits
Access
Factory
Code
Write
Read
Scroll
High
Low
Incr
Parameter
Settings
153
0
0
NO
2088
1989
1
Set Time Clock - Year
2001
•
Enter the four digits of the current year.
Security
Limits
Access
Factory
Code
Write
Read
Scroll
High
Low
Incr
Parameter
Settings
154
0
0
YES
12.31
1.01
1.1
Set Time Clock - Month . Day
1.01
•
Enter the month to the left and the day to the right of
the decimal point.
•
If the number of the day is a single digit, the digit
must be preceded by a zero.
Security
Limits
Access
Factory
Code
Write
Read
Scroll
High
Low
Incr
Parameter
Settings
155
0
0
YES
23:59
0:0
0:01 Set Time Clock - Hour : Minute
1:01
•
Enter the hour and minutes based on 24-hour nota-
tion.
Security
Limits
Access
Factory
Code
Write
Read
Scroll
High
Low
Incr
Parameter
Settings
156
0
0
YES
:59
:00
:01
Set Time Clock - Seconds
:00
•
If the number of seconds is a single digit, the digit is
preceded by a zero.
High-Current Lockout (cont’d)
Security
Limits
Access
Factory
Code
Write
Read
Scroll
High
Low
Incr
Parameter
Settings
143
1
0
YES
4
1
--
High-Current Lockout - Phase
4
(Active Trip Number)
143
1
0
YES
4
1
--
High-Current Lockout - Ground
4
(Active Trip Number)
•
Indicates on which trip operation the high-current
lockout is active.
•
Use PHASE/GROUND key to examine phase and
ground.
When the Form 4C control is first energized, the clock default
date is January 1, 2001 (1/1/2001). The clock must be set to
the proper date and time for the events to be properly record-
ed. (Refer to
Setting The Control Clock
section of this manual.)
IMPORTANT:
Overcurrent protection is independent
of the clock and will respond correctly regardless of the
clock status.