52
Kyle Form 4C Microprocessor-Based Recloser Control Programming Guide
Security
Limits
Access
Factory
Code
Write
Read
Scroll
High
Low
Incr
Parameter
Settings
166
--
0
YES
--
--
--
Ground Current (kA)
--
•
Access Code 166 identifies the ground current of the
event indicated by Access Code 161.
•
Access Code 166 can only be accessed from
Access Code 161 using the SCROLL key.
Security
Limits
Access
Factory
Code
Write
Read
Scroll
High
Low
Incr
Parameter
Settings
167
--
0
YES
--
--
--
Phase Bushing1-2 Current (kA)
--
168
--
0
YES
--
--
--
Phase Bushing 3-4 Current (kA)
--
169
--
0
YES
--
--
--
Phase Bushing 5-6 Current (kA)
--
•
Access Codes 167 through 169 identify the current
through the three phases of the event indicated by
Access Code 161.
•
Current values are in rms kiloamperes. Current range
is from 0 kA to 30 times programmed minimum trip
value. If the fault exceeds 30 times minimum trip, an
over-range message (-1) will be displayed.
•
Access Codes 167 through 169 can only be
accessed from Access Code 161 using the SCROLL
key.
Event Recorder (cont’d)
Security
Limits
Access
Factory
Code
Write
Read
Scroll
High
Low
Incr
Parameter
Settings
165
--
0
YES
--
--
--
Second
--
•
Access Code 165 identifies the second of the event
indicated by Access Code 161.
•
Access Code 165 can only be accessed from
Access Code 161 using the SCROLL key.