54
Kyle Form 4C Microprocessor-Based Recloser Control Programming Guide
Load Profile Monitor
Security
Limits
Access
Factory
Code
Write
Read
Scroll
High
Low
Incr
Parameter
Settings
180
0
0
NO
96
1
1
Load Profile - Reading Number
--
•
Data is accessible through the keyboard or Digital
Communications.
•
From the keyboard, Access Codes 181 through 185
are accessible from Access Code 180 using the
SCROLL key.
•
Data is read and recorded in 15-minute intervals and
stored in memory for the most recent 24 hours for a
total of 96 readings.
•
Indicates the rms demand current for each phase
and ground.
•
No security code is required for readout.
IMPORTANT
:
Load Profile Data will be lost
if power to the Form 4C control is lost. Load
Profile data will also be lost when the control
resets after a change to a TCC Group (Access
Code 70) or Line Frequency (Access Code 71).
Security
Limits
Access
Factory
Code
Write
Read
Scroll
High
Low
Incr
Parameter
Settings
181
--
0
YES
--
--
--
Time - Hour and Minute
--
•
Indicates the hour and minute of a specific phase
rms demand current profile.
Phase Current
Phase Current
Phase Current
Reading
Hr:Min
Ground Current
Bushing 1-2 (A)
Bushing 3-4 (A)
Bushing 5-6 (A)
(180)
(181)
(182)
(183)
(184)
(185)
1
15:30
2
258
261
262
2
15:15
0
260
257
259
3
15:00
2
253
251
255
4
14:45
1
261
255
257
5
14:30
1
257
248
257
TABLE 10
Load Profile Monitor Sample Data