Mounting the enclosure
The WaveLinx Wired modules consist of an enclosure with
interior DIN rail modules. Interior DIN rail modules include:
• SCMA0401-NA: 4 120V-277V dimmers
ote:
N
Ensure at least three(3) inches of air space around the
WaveLinx Wired enclosure.
Class 2
Low voltage Input
Class 2
Low voltage Input
Class 1 and Class 2
High and Low
voltage Input/Output
Class 1 and Class 2
High and Low
voltage Input/Output
Location and spacing
The WaveLinx Wired models are all fully convection cooled;
therefore it is vitally important to ensure that each unit is
installed in a ventilated location that permits sufficient airflow
and provides the correct operating conditions.
The cabinets do not contain fans. Allowing airflow around the
panel will enhance the reliability and longevity of all models.
Locating panels away from heat generating equipment will also
benefit long term reliability. Also ensure that the stated ambient
atmosphere requirements are not exceeded.
Ambient atmosphere requirements
• Temperature 32°F to 104°F (0° C to +40° C)
• Humidity 0 to 95% non-condensing
Mounting considerations
• A minimum of 14 inches (360 mm) must be maintained
from the front of the chassis to any other components or
walls. Please make sure to check and follow local code
requirements if additional clearance is needed per code in
your area
• Allow adequate space for future maintenance of the unit. Do
not install in a location that will later be difficult to access
• The WaveLinx Wired panel is designed to be mounted
vertically
• Use suitable conduits and couplers to link the raceways to
the controller chassis
To mount the enclosure
1. Choose a dry location convenient to the circuit breaker
panel that meets the operating temperature requirements.
2. Mount the panel on a firm surface using the predrilled
holes.
3. Connect the enclosure to the circuit breaker panel using
conduit.
4. Remove all cuttings and dirt.
ote:
N
Make certain that high voltage and low voltage load
wiring enters the enclosure separately. High voltage
wiring should be brought into the enclosure through the
left and right sides or the top right and top left wiring
channels. Low voltage wiring can be brought into the
enclosure from the top-middle or bottom middle location
of the enclosure.
ote:
N
Ensure at least three(3) inches of air space around the
WaveLinx Wired enclosure.
3 INCH SPACE AROUND ENCLOSURE PANEL
SMALL
12.00
6.00
8.75
Ă .25
2X
Ă .44
2X
3.75
.25
2X
3 INCH SPACE AROUND ENCLOSURE PANEL
MEDIUM
16.00
22.88
Ă .91
2X
Ă .41
2X
10.75
8.00
.41
2X
IL Area Controller with SCMA0401 Adaptive Dimmer
WaveLinx Wired
IB50301922 page 3