Connecting to the lighting network
Medium and large WaveLinx Wired panels include the CR1-RJ PC connection device. A PC can be connected to the WaveLinx Wired
panel using the SW2 cable kit plugging into the RJ port on the CR1-RJ. If this WaveLinx Wired panel is connected to the lighting
network the PC will have access to all WaveLinx Wired devices on the lighting network.
In a medium or large WaveLinx Wired panel one side of the CR1-RJ will not have wires connected. This terminal is used to connect to
other WaveLinx Wired panels. The lighting network is a daisy-chain and requires one in and one out connection. The lighting network
also requires a terminating jumper installed at the two ends of the network
Lighting network wire should use Cooper Lighting Solutions LCCP or LCCNP wire (alternate: Belden 1502, 1502P).
Lighting network wiring detail
Wiring Information:
Wire size: 18-22AWG
Solid/stranded copper only
Class 2 wiring
Wire:
Use Cooper Lighting Solutions catalog # LCCP or LCCNP
Alternate: Beldon 1502 or 1502P or equal
Run five wire
network wire to
additional
WaveLinx Wired
panels maintain
daisy chain
Class 2
Field installed
five wire
network wire
Class 2
Prewired five
wire network
wire
*Note: Lighting control network must be run as a daisy
chain, with termination jumper in place at two ends.
Strip wire: 1/2” to 5/8”
Device
Device
WaveLinx
Wired
lighting
panel
Termination
ON
TERM
TERM
Termination
OFF
Device
T
T
IL Area Controller with SCMA0401 Adaptive Dimmer
WaveLinx Wired
IB50301922 page 6
May 2022
www.cooperlighting.com