AGL_Ref_ST_YBK1E_EN_Rev01
5
2.4.3 PED category and maximum allowable pressure PS
The nameplate of the compressor contains information about the maximum allowable pressure PS,
the minimum and maximum allowed temperature TS, the internal f ree volume and the f luid groups
of the ref rigerants qualified for the compressor model range. Values are given f or the two existing
pressure ranges on low- and high-pressure side.
Compressor
PS
Low-pressure
side
PS
High-pressure
side
TS max.
Low-pressure
side
Internal free
volume
LP side (litres)
Internal free
volume
HP side (litres)
YB12K1E
23.5 bar(g)
38 bar(g)
50 °C
4.1
0.5
YB17K1E
23.5 bar(g)
38 bar(g)
50 °C
4.2
0.5
YB21K1E
23.5 bar(g)
38 bar(g)
50 °C
4.3
0.5
YB24K1E
23.5 bar(g)
38 bar(g)
50 °C
4.8
0.5
YB31K1E
23.5 bar(g)
38 bar(g)
50 °C
6.4
0.6
YB36K1E
23.5 bar(g)
38 bar(g)
50 °C
6.4
0.6
Table 5: Maximum allowable pressures, temperatures and internal free volume s
The PED category is assigned according to the Pressure Equipment Directive PED 2014/68/EU.
Requirements apply to the relevant pressure levels in the compressor if a limit value for the product
of pressure relative to the environment and relevant internal f ree volume is exceeded. For the
calculation of the PED category, a differentiation must be made between the high- and low-pressure
sides. The highest of the calculation results is considered to determine the PED category .
YB*K1E scroll compressors can be operated with both A1 and A2L ref rigerants. To determine the
PED category a distinction is made between ref rigerants of f luid group 1 (f lammable) and f luid
group 2 (non-flammable). As a result, identical compressor models may be subject to different PED
categories depending on the refrigerant used.
Compressor range
Refrigerant
Fluid group
PED class
YB*K1E
R454C, R455A, R454A,
R1234yf
1
2
R404A, R407A, R407F,
R448A, R449A, R407C,
R513A, R134a, R450A
2
1
Table 6: PED class based on refrigerant used