background image

950-779-115-02, Revision 02

 

Fault Isolation

PRL-770 and PRL-779 List 1E and 2E

March 17, 2000

 13

S

UBSCRIBER

 R

EPORTED

 F

AULTS

Use the craft interface to initiate a subscriber drop test to determine the cause of any of the following problems. 
The subscriber drop test performs Hazardous Potential, Foreign Voltage, Resistive Faults, Receiver Off-Hook, 
and Ringers Tests. 

Table 2

 provides procedures for isolating faults, based on subscriber reports.

M

argin

Flashing

distance limitation exceeded

1

Initial installation, check engineering records for distance between COT 
shelf and RT.

fault in HDSL line

2

If existing installation, measure loss of HDSL line to ensure that the 
maximum attenuation value has not been exceeded.

faulty RT

3

Replace the COLU or the RT or both.

SYNC

Off

HDSL line has lost 
synchronization

1

Initial installation, check engineering records for distance between COT 
shelf and RT.

distance limitation may have 
been exceeded

2

If existing installation, measure loss of HDSL line to ensure that the 
maximum attenuation value has not been exceeded. 

COLU is faulty

3

Replace the COLU or the RT or both.

PWR

Off

no input power

1

Ground fault condition exists.

on-board fuse is blown on 
COLU

2

Check input COT power at COT shelf backplane with COLU removed.

3

If power is present at COT shelf backplane, replace the COLU.

PWR

Flashing

HDSL line open

1

Check line continuity and resistance. 

an overload exists

2

COLU power supply or RT may be faulty.

Table 2.

Subscriber Fault Isolating

Conditions

Causes

Procedures

no dial tone, 
cannot dial

Short-circuit or 
open-circuit

1

At the CO using the craft interface, select Test menu option, and view the test 
results. The tests run are for Hazardous Potential, Foreign Voltage, Resistive 
Fault, and CPE Termination.

faulty COLU or RT

2

Check for shorts or opens towards the subscriber or on the customer 
premise.

3

Lift the jumper in the CO between the CO switch and the COT shelf. If dial tone 
is present at the switch, replace the COLU.

4

If after replacing the COLU the dial tone is still not present, the fault is in the 
RT. Replace the RT.

Phone does 
not ring

high-resistance short on 
subscriber drop (REN load 
exceeded, see 
Specifications)

1

At the CO, using the craft interface, go to the COLU Main screen to verify the 
correct operation of the COLU. If you cannot view the COLU Main screen, a 
communication error exists indicating a faulty COLU. Remove and re-insert 
the COLU. 

faulty RT or COLU

2

Go to the Test menu option, and select the desired circuit to test.

3

View the subscriber drop test results. Refer to the Test Submenu section for 
specific results.

4

Check for ringing on another line terminated on the same RT. If ringing is 
present on other lines, check for high-resistance shorts on the subscriber 
drop. If no high resistance shorts, replace the RT.

5

If ringing is not present on another circuit terminated on the RT, lift the jumper 
between the CO switch and the COT shelf. If ringing is present, replace the 
COLU. If ringing is not present, the fault is in the switch.

Table 1.

COLU LED Fault Isolating (Cont.)

LED

Mode

Condition

Procedure

Summary of Contents for 150-1670-52

Page 1: ...ENGINEERING SERVICES TECHNICAL PRACTICE 950 779 115 020 SECTION 950 779 115 02 Indoor Remote Terminal Enclosure PRL 770 List 2E PRL 779 List 1E Part Number 150 1670 52 150 1679 51 CLEI Code S9MSBA0A...

Page 2: ...ll assert no such right license or interest with respect to such trademark All other product names mentioned in this document are used for identification purposes only and may be trademarks or registe...

Page 3: ...y and to PairGain Order replacement equipment if necessary Check the packing list to ensure complete and accurate shipment of each listed item If the shipment is short or irregular contact PairGain as...

Page 4: ...Inspecting Your Shipment 950 779 115 02 Revision 02 iv March 17 2000 PRL 770 and PRL 779 List 1E and 2E...

Page 5: ...t Equipment 4 Preparing the RT 5 Mounting the RT 5 Wall Mounting 5 Line up Mounting 7 Wiring the RT 9 Turn up and Testing 12 Fault Isolation____________________________________________________________...

Page 6: ...Table of Contents 950 779 115 02 Revision 02 vi March 17 2000 PRL 770 and PRL 779 List 1E and 2E...

Page 7: ...LS GS lines each for as many as 96 subscriber lines The COT shelf operates on standard 48 Vdc CO battery and supplies power to the RT eliminating the need and expense of providing local power at the...

Page 8: ...d to establish a path to channel 1 of the LS GS RT during fault conditions and to provide for drop testing of the selected subscriber line from the CO location SPECIFICATIONS Power Voltage Safety A2 c...

Page 9: ...oop Current 23 mA minimum Ring Generation PRL 770 Balanced Trapezoidal 40 Vrms minimum 20 3 Hz up to 5 REN per line 10 REN total at RT PRL 779 Unbalanced Trapezoidal 40 Vrms minimum 20 3 Hz up to 5 RE...

Page 10: ...performed by qualified service personnel only This RT is to be installed in a restricted access location Be careful when installing or modifying telephone lines Dangerous voltages can be present It is...

Page 11: ...e Mounting Kit for the RT wall positioning The RT is now prepared for mounting MOUNTING THE RT The PRL 770 and PRL 779 are suitable for mounting on a wall or line up Wall mounting is preferable Wall M...

Page 12: ...2 6 March 17 2000 PRL 770 and PRL 779 List 1E and 2E Use the two No 6 x 1 inch wood screws provided in the Mounting Kit to attach the RT to the wall of the restricted access area see Figure 3 Figure 3...

Page 13: ...L 770 and PRL 779 List 1E and 2E March 17 2000 7 Line up Mounting Use the back panel of the enclosure or the enclosed hole pattern drawing as a template for marking the locations of mounting holes as...

Page 14: ...8 March 17 2000 PRL 770 and PRL 779 List 1E and 2E Use the two No 6 x 1 inch wood screws provided in the Mounting Kit to attach the RT to the side of the restricted access area see Figure 5 Figure 5 L...

Page 15: ...ip and Ring wires attaching the subscriber line wires During installation refer to the RT Reference label see Figure 6 affixed inside the Telco Access door The Reference label identifies the Frame Gro...

Page 16: ...nsert the Tip and Ring wires through the hole below the Telco Access door This RT does not provide primary protectors on the HDSL or subscriber pairs The primary protection for HDSL pairs must be an i...

Page 17: ...g holes see Figure 8 Each wire entry hole accepts one unstripped solid copper wire 22 24 American Wire Gauge AWG with a maximum insulation diameter of 1 52 mm Figure 8 Attaching the RT Wires 4 Press t...

Page 18: ...to determine the cause of any of the following problems Table 1 provides procedures for isolating faults indicated by the COLU LEDs Table 1 COLU LED Fault Isolating LED Mode Condition Procedure None O...

Page 19: ...y be faulty Table 2 Subscriber Fault Isolating Conditions Causes Procedures no dial tone cannot dial Short circuit or open circuit 1 At the CO using the craft interface select Test menu option and vie...

Page 20: ...hone loop length too long 2 If phone does not stop ringing when using a butt set at the subscriber location one or both of these conditions exist faulty RT loop length is too long refer to Specificati...

Page 21: ...Central Office Terminal ESD Electrostatic Discharge HDSL High bit rate Digital Subscriber Line IDC Insulation Displacement Contact LED Light emitting Diode LS GS Loop Start and Ground Start MLT Mechan...

Page 22: ...ts will operate substantially in accordance with the PairGain published specifications and documentation for such software PairGain s entire liability for software that does not comply with the forego...

Page 23: ...y PairGain the Buyer will be responsible for payment of the cost of the replacement product BILLING PairGain s repair of products returned for repair replacement or credit whether in warranty or out o...

Page 24: ...ason for the return For example The equipment needs an ECO ECN upgrade The equipment is defective If there is another reason for returning the equipment please let us know so we can determine how best...

Page 25: ...se harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interfe...

Page 26: ...Corporate Office 14402 Franklin Avenue Tustin CA 92780 Tel 714 832 9922 Fax 714 832 9924 For Technical Assistance 800 638 0031 714 730 3222...

Reviews: