CH1001-A Chiller Operator’s & Installation Manual
© 2002-2010, IMI Cornelius Inc.
- 1 -
Publication Number: 620914301
GENERAL INFORMATION
I
NTRODUCTION
The Cornelius ”CH” Series Recirculating Water Chiller is designed to provide an accurate, reliable, and user-
friendly system for cooling a continuous flow of pure liquid and keep that liquid at a constant temperature in
various closed loop or tank cooling applications.
The ”CH” Series Chiller consists of an air–cooled refrigeration system housed in a sturdy sheet metal frame and
cabinet. A standard pump and insulated water reservoir package provides a complete water cooling and
circulating system.
The ”CH” Series Chiller is designed to operate in a clean laboratory or industrial environment where ambient
temperatures range from 40 to100° F (5 to 38° C). With proper installation, operation, and maintenance, the ”CH”
Series Chiller will provide years of trouble free service.
U
NPACKING
AND
I
NSPECTION
This unit was thoroughly inspected before leaving the factory and the carrier has accepted and signed for it. Any
damage or irregularities should be noted at the time of delivery and immediately reported to the carrier. Request
a written inspection report from the Claims Inspector to substantiate any necessary claims. In the event that an
immediate replacement is necessary, please contact Cornelius Chiller Sales at 1–800–551–4423.
D
ESIGN
D
ATA
D
ATA
P
LATE
I
NFORMATION
Figure 1. Sample Data Plate
Table 1. Design Data
CH1001-A
Cooling Capacity:
BTU/hr (W) at 80° F (27° C) and 70° F
(21° C)
12,000 (3,515)
Compressor Horse Power
1 (.746 kW)
Electrical Data:
Voltage/Phase/Hertz/Amperage
230/1/60, 11 Amps
Refrigerant Type:
R134a
Reservoir Capacity (Gal)
6.0 (22.7 liters)
Dimensions: Depth (inches)
Width (inches)
Height (inches)
26-1/2 (67cm)
22 (56cm
38-1/4 (97cm)
Process Connections
3/4-inch FPT (S/S)
Optimum Process Liquid Flow GPM
(Liters/Min)
2.4 (9.0)
Condenser Air Flow (CFM)
712