background image

 

Dual  SGHN4  Series 

REVISION  #  0000 

DATE: 05/29/2018 

 
Disconnect power at the fuse box before proceeding with any wiring.   

 

 

2.  Locate the control station where the user can 

clearly see the operation of the door. Mount the 
enclosed placard adjacent or near the door. 

                               

Controls shall be far enough from the door, or positioned such that the user 
is prevented from coming in contact with door while operating the controls. 

 

3.  Do not run control wiring in the same conduit as power wiring. 

 

4.  Any wire connected to the control panel must be protected by conduit or other means to ensure the 

safety and permanency of the wiring. 

 

 

Do not use radio controls with your operator unless some type of 
entrapment protection device has been installed. Failure to do so may result 
in serious injury or death to person(s) trapped beneath the door. 

 
 

 

Changing from left hand to right hand or vice versa could result in change 
of control wiring.    Consult factory for details. 

 

5.  After installation, be sure that the operator, controls, and sensing edge or other entrapment 

protection devices have been tested and function properly. 

 

WARNING

 

 

WARNING

 

 

WARNING

 

 

WARNING

 

Summary of Contents for SGHN4 Series

Page 1: ...INSTALLATION INSTRUCTIONS AND OPERATION MANUAL SGHN4 100 Series Dual Operator NEMA 4 12 UL325 2010 Compliant Commercial and Industrial Door Operator Logic Control Continuous Duty ...

Page 2: ...or any other adjacent walking surface and c away from all moving parts of the door 7 Install the Entrapment Warning Placard next to the control station in a prominent location 8 Make sure the available power supply to be connected to the operator is of the same voltage frequency phase and wattage as indicated on the nameplate of the operator 9 Read and understand the wiring diagram of the operator...

Page 3: ...Hoist Standard ENTRAPMENT PROTECTION Sensing Edge Optional Sensing device attached to the bottom edge of the door Non Contact Device Optional Photo eye device Per the requirements of UL Standard 325 the door operator is setup for constant pressure to close the door As an alternative the door may be provided with a monitored entrapment protection device that will reverse the door upon contact with ...

Page 4: ...ms 4 While pressing the spring loaded lever G which holds the limit switch cams in place adjust the limit switch cam E or F until the micro switch C or D clicking sound is heard 5 If the limit switch cam cannot be rotated to its desired position release the lever and move the door away from the desired position then adjust the limit switch cam to its desired position It may be necessary to repeat ...

Page 5: ...nected to the control panel must be protected by conduit or other means to ensure the safety and permanency of the wiring 5 Use copper wire inside the control panel 6 A separate circuit of adequate capacity is needed for the operator 7 The operator must be properly grounded The ground screw painted green is located inside the control panel Failure to properly ground the operator could result in el...

Page 6: ...r Entrapment Device Options Sensing Module Device Manufacturer Model ELR 2 wire resistive sensing edge Miller Edge Inc End of Line resistor type edge must have model number with Suffix T2 ME110 ME111 ME120 ME123 ME112 ME113 ME116 ME117 MT21 MU21 MT22 MU22 MC22 MU33 MC271 CPT223 MEL RB G K10 ASO GE225 GE125 GE245 GE F45 GE F50 GE F56 GE F65 GE F85 GE F115 IR Monitored photo eye FRABA Inc Optical Ed...

Page 7: ... power wiring 4 Any wire connected to the control panel must be protected by conduit or other means to ensure the safety and permanency of the wiring Do not use radio controls with your operator unless some type of entrapment protection device has been installed Failure to do so may result in serious injury or death to person s trapped beneath the door Changing from left hand to right hand or vice...

Page 8: ... s u r e C l o s e O n O f f A u t o O p e n S a f e t y S w i t c h ON OFF ON OFF ON OFF A A 2 1 Stop 2 Open 3 Close 4 Com 7 8 Close Warning signal 24VDC A 1 1 2 3 4 7 8 9 10 23 24 P5 P6 E5 E6 IR P5 P6 ELR E5 E6 ELR End of line resistor L1 L2 L3 Three phase power source See operator plate for correct voltage A 3 1 2 3 4 7 8 9 10 23 24 P5 P6 E5 E6 9 10 Extemal Interlock 23 24 Timer Defeat CN26 Opt...

Page 9: ...io control B 3 B Open door Stop door Close door B 2 Open door Stop door Close door B 2 24VAC Push button 24VAC B 1 4 3 2 1 1 1 2 Open limit dry contact 2 3 4 Close limit dry contact 2 1 2 1 CN12 CN13 CN14 24VDC MAX 0 5A B 1 24VDC MAX 0 5A Non Monitored Sensing Devices N O Dry Contact ...

Page 10: ... counting when door leaves close limit Door stops after opening for set time Pressing open again at mid open position will cause door to open to open limit T2 Timer to close Timer is active when door stops and is not at close limit T3 Door Open Warning Timer Timer is active when door leaves close limit When time is up contact will close See figure C 1 Terminals 23 and 24 External timer disable swi...

Page 11: ...ime Max 99 Sec T1 T2 Mid Open Timer Max 99 Sec Min 1 Sec T1 T1 T1 T3 T3 T1 T1 T1 T2 T3 3 To Set Timer 2 Timer to close Remove jumper from terminal 23 24 to enable Timers Turn timer switch S10 to ON Switch M CL switch to ON See figure A 2 on Page 13 for location Press T2 and hold for 5 seconds Display will flash Use and to increase or to decrease time Press T2 to save setting Without pressing no ad...

Page 12: ...ithout pressing no adjustment is saved Min 1 Sec Min 1 Sec Set the desired time T1 T2 T1 T2 Door Open Warning Timer T3 Max 99 min 59 Sec Max 99 min 59 Sec T3 T1 T2 T3 T3 T3 T3 T3 T3 T3 5 To confirm timer value Set Mode Set Mode Set Mode Select Time r T1 T2 T3 T1 T2 T3 T1 T2 T3 T1 T2 T3 T1 T2 T3 Note To enable timer s 1 Must switch Timer Switch S10 to ON See figure A 2 on Page 7 for location 2 Must...

Page 13: ...close limit OFF Not at AUX close limit LED5 Door close limit ON Door at close limit OFF Not at close limit LED8 Device light ON When any one of sensing device is normal OFF Safety device disconnected failed or damaged LED17 Open button ON Activated OFF Not activated LED18 Close button ON Activated OFF Not activated LED16 Control station stop ON Connect with 3 button control station and not activat...

Page 14: ...13 Dual SGHN4 Series REVISION 0000 DATE 05 29 2018 ...

Page 15: ...14 Dual SGHN4 Series REVISION 0000 DATE 05 29 2018 LS1 LS2 LS3 LS4 ...

Page 16: ...cted Control panel is wired with momentary pressure open and constant pressure close A one second delay on reverse is standard When the door is closing pushing the Open or Stop button will stop the door from moving When the door is closing the radio control transmitter can stop and reverse the door at anytime TB2 BOX A 1 2 3 To Box B TB11 terminal TB3 BOX A 1 2 3 To Box C TB21 terminal TB5 BOX A 1...

Page 17: ...ox C TB23 terminal TB11 BOX B 1 2 3 To Box A TB2 terminal TB12 BOX B 1 2 3 To Box A TB6 terminal TB13 BOX B 1 2 3 4 5 6 7 8 9 10 11 12 13 14 To Box A TB5 1 5 terminal Spare To Box A TB5 7 11 terminal Spare To Box A TB5 13 14 terminal TB21 BOX C 1 2 3 To Box A TB3 terminal TB22 BOX C 1 2 3 To Box A TB7 terminal TB23 BOX C 1 2 3 To Box A TB8 terminal ...

Page 18: ...nth After adjusting either the force or the limit of travel retest the door operator s safety features Failure to adjust the operator properly may cause severe injury or death 5 For products having a manual release if possible use the manual release only when the door is closed Use caution when using this release when the door is open Weak or broken springs may cause the door to fall rapidly causi...

Page 19: ...n to stop movement of the door while opening or closing Removing pressure from the CLOSE key position will cause the door to stop 3 Door may also be operated by remote devices EMERGENCY MANUAL OPERATION This operator has provisions for manually operating the door in case of emergency or power failure This operator is equipped with an auxiliary hoist To operate the hoist 1 Remove the hand chain fro...

Page 20: ...Lubricate Sprockets Check set screw tightness Fasteners Check tighten as required Bearings Shafts Check for wear lubricate Do not lubricate motor Lubrication could cause damage Inspect and service whenever a malfunction either door or operator is observed or suspected Before servicing always disconnect power supply to the operator Replace fuses only with those of the same type and rating All repla...

Page 21: ... Devices Connection Instruction Dual Photo eyes Connection Module Dual photo eyes connection module connects on CN3 Two module provide photo eyes devices x4 connection require a wire Harness to CN3 Unplug the jumper connector to add modules Plug back the jumper connector if no additional module is used 1 2 or Primary Sensing Device Connection 1 2 3 Part No GW40 05 02 3 Part No GW40 05 02 ...

Page 22: ... OPEN Key switch B2 COM Warning Please Remove Jump Pin First See A A Remove Jump pin OPEN CLOSE STOP OPEN CLOSE KEY REQUIRED TO REMOVE COVER S T O P S T O P R BK R WH OPEN CLOSE NC NO C NC NO C STOP WH WH GR KEY SWITCH COM OPEN CLOSE KEY REQUIRED TO REMOVE COVER S T O P S T O P Key Switch with Stop Button and 3 Button Stations Key Switch with Stop Button Control Wiring for Key Switch with Stop But...

Page 23: ... B2 B1 OPEN CLOSE STOP KEY ON OFF OPEN CLOSE STOP KEY LOCKOUT 3 2 BUTTON B1 B2 1 2 3 4 OPEN OPEN CLOSE CLOSE B2 B1 STOP B2 STOP B1 R BK GR KEY LOCKOUT 3 BUTTON 1 2 3 4 OPEN CLOSE STOP Key switch Key switch R WH GR BK STOP CLOSE OPEN ON OFF R2 R1 RADIO R3 R2 R1 Ceiling Pull Switch Station 1 4 CLOSE OPEN CLOSE OPEN R1 R3 R2 GR WH 3 2 1 WH BK GR WH BK Control Connections Diagrams 1 2 3 4 1 2 3 4 1 2 ...

Reviews: