10.4
. To test the remaining portions of the system (Figure 17):
Step 1:
Install the
Light Source/RJ1 LC connector adapter
onto LC number 2 of the
harness plugged into the LIVE Port of the MTP Tap module.
Step 2:
Install
Meter 1/RJ2’s LC connector
into the number 1 port of the EDGE8 module,
Module “B”.
Step 3:
Install
Meter 2/RJ3’s LC connector adapter
onto LC number 1 of the harness
plugged into the TAP port of the MTP Tap module.
Step 4:
Continue testing through on the even fibers of the harness plugged into the
front-mounted LIVE Port of the MTP Tap module using Tables 2 and 4 for testing
sequences.
Module harness
TAP port
test harness
RJ1
and
adapter
RJ2
RJ3
and
adapter
Do NOT
disconnect
EDGE8 Module “B”
HPA-1007-EDGE8
multimode only
B
2
3
B
1
2
1
A
M1
Do NOT
disconnect
0.00 dB
Light
Source
“Near end”
“Far end”
EDGE8 MTP Tap Module “A”
Note: Fiber loss
depends on length
of system
LC #8
LC #8
LC #2
M2
Do NOT
disconnect
0.00 dB
LC #1