background image

 

 

 

I ns t al l at i o n G u id e li n es   C MA - XX X- A E N 

P a ge   1 8 

 

 

Draft 

3.4.4 

Cable Routing   

Ensure all cables, e.g. power cable, feeder cable, optic fiber, commissioning cable, connecting are properly routed and secured 
so that they are not damaged. 

3.5

 

RF Coaxial Cable Guidelines 

3.5.1 

General RF Cable Installation Procedures 

Note: The installer should be familiar with the ANSI/TIA/EIS-568 Cabling Standard guidelines.   

 

Observe the general cable installation procedures that meet with the building codes in your area. The building code requires 

that all cabling be installed above ceiling level (where applicable). The length of cable from the risers to each antenna must 
be concealed above the ceiling.   

 

The cable must be properly supported and maintained straight using velcro cable ties, cable trays and clamps or hangers 

every 10 feet (where practical above ceiling level). Where this is not practical, the following should be observed: 

 

The minimum bending radius of the supplied ½” coax cable should be 7”. 

 

Cable that is kinked or has a bending radius smaller than 7” must be replaced. 

 

Cable runs that span less than two floors should be secured to suitably located mechanical structures. 

 

The cables should be supported only from the building structure. 

 

All cables shall be weather-resistant type

 

 

Cable length - determined by the system installation plan. When calculating the cable length, take into account excess 

cable slack so as not to limit the insertion paths. 

3.5.2 

RF Rules 

 

Use coax RG-223, 50 ohm, male-to-male N-type to QMA for RF connections from the RIMs to the BTS/RBS and to the 

MRU. 

 

When using the Corning remote unit in an environment in which other indoor coverage systems are installed, it is 

recommended (where possible) that the antennas are placed at least two meters apart   

 

When bending coax cables, verify that the bending radius does not exceed the coax specifications. 

 

Use wideband antennas supporting a range of 300 MHz to 3 GHz   

 

Terminate all unused MRU RF ports with a 50 ohm load 

 

Make sure that the VSWR measured at the coax cable meets the product specification The VSWR must be measured prior 

to terminating the MRU RF ports in the remote communication rooms.

 

3.5.3 

Coax Cable Lengths and Losses 

Use coax RG-223, 50 ohm, for RF connections between MRU unit and DAS antennas. 

Note: The required distance between the antennas (installed in the ceiling) depends on the infrastructure and calculated 
path-loss. For example, if there is free space-loss between the antennas, a minimum distance of 100 ft is required; if there are 
partitions (loss) between the antennas, a distance of less than 100 ft between them is allowed. 

Coax Length 

Coax Loss 

 

(900 MHz) 

Connector 

Loss 

Total Loss 

30 

0.7 

1.5 

2.2 

40 

0.9 

1.5 

2.4 

50 

1.1 

1.5 

2.6 

60 

1.3 

1.5 

2.8 

Summary of Contents for MRU

Page 1: ...Table of Contents CMA xxx AEN Page 1 Corning Mid Power Remote Unit MRU User Manual ...

Page 2: ...Hardware Warranty Period the Hardware Warranty Period for such repaired or replaced components shall extend to the longer of i the balance of the Hardware Warranty Period or ii three 3 months from the date of repair or replacement For purposes of this Warranty Specifications shall mean the specifications and performance standards of the Products as set forth in documents published by Corning and d...

Page 3: ...s and otherwise conveys to Customer provided however that Corning itself provides no warranty of any kind express implied statutory or otherwise for any third party software provided hereunder Corning does not warrant any hardware software or services not provided by Corning THIS WARRANTY IS THE ONLY WARRANTY MADE BY CORNING AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING BUT N...

Page 4: ...nstructed to prevent as far as reasonably practicable danger Any work activity on or near equipment involving installation operation or maintenance must be as far as reasonably free from danger Where there is a risk of damage to electrical systems involving adverse weather extreme temperatures wet corrosive or dirty conditions flammable or explosive atmospheres the system must be suitably installe...

Page 5: ...length window External optical power is less than 10 mW Internal optical power is less than 500 mW To avoid eye injury never look directly into the optical ports patchcords or optical cables Do not stare into beam or view directly with optical instruments Always assume that optical outputs are on Only technicians familiar with fiber optic safety practices and procedures should perform optical fibe...

Page 6: ...es and Capabilities 9 1 2 General System Specifications and Requirements 10 1 2 1 Environmental and Regulatory Specifications 10 1 2 2 Safety and Regulatory Approvals 10 1 2 3 Power Specifications 10 1 3 System Architecture 11 1 4 System Monitoring and Management 12 2 MRU Interfaces 13 3 Installation Guidelines 16 3 1 Site Considerations 16 3 2 Safety Guidelines 16 3 3 Installation Requirements 16...

Page 7: ...21 3 9 Manual Handling 21 4 Installation 22 4 1 Unpacking and Inspection 22 4 2 Mounting the MRU 23 4 2 1 Rack Installation 23 4 2 2 Wall Mount Installation 24 4 2 2 1 Unpacking and Inspection 24 4 2 2 2 Mounting MRU on Wall 25 4 2 3 Outdoor Installation 27 4 2 3 1 Items Required for Outdoor Installation 27 4 2 3 2 Pre Installation Procedures 28 4 2 3 3 Install MRU in Cabinet 29 4 3 Grounding MRU ...

Page 8: ...pecifications 42 Supported Services 42 RF Parameters 42 Coupling Specifications 43 Environmental 43 Standards and Approvals 43 Optical 43 Physical Specifications 44 6 Appendix B Ordering Information 45 MRU Assembly Configurations 45 MRU Stand alone Modules 45 Accessories 45 Cable Assembly 46 ...

Page 9: ...The HCM enables centralized single source local and remote management of all system elements Figure 1 1 Mid Power Remote Unit MRU 1 1 Key Features and Capabilities Multi frequency multi service platform supports up to six SISO bands Accommodates GSM UMTS LTE and more Multi operator optimized platform services from a number of operators can be distributed by the same unit Cost effective higher powe...

Page 10: ...cept for deviations pursuant to laser notice no 50 and IEC 60825 1 EMC FCC 47 CFR Part 15 22 24 27 Safety UL 60950 IEC 60825 1 2007 IEC 60825 2 2010 CAN CSA C22 2 No 60950 1 03 NEBS GR 63 GR 1089 Table 1 2 Safety and Regulatory Approvals 1 2 3 Power Specifications Power Spec Description Power consumption max 360 W for fully loaded chassis AC Power input 100 240 VAC 50 60 Hz Max current consumption...

Page 11: ... radio interface modules RIM ensuring a constant RF level The conditioned signals are then converted by the optical interface modules OIM to an optical signal for transporting over single mode fiber to the MRU at the remote location In the uplink the process is reversed All mobile services are combined and distributed through a single antenna port over the broadband antenna infrastructure installe...

Page 12: ...via the headend control module SW management application v1 6 and higher Figure 1 3 shows the management tabs of the selected MRU unit Refer to the HCM and Web Management User Manual v1 6 and higher for information on how to configure and manage the MRU remote unit Figure 1 3 Example of MRU Management GUI ...

Page 13: ... pre installed in designated slots according to supported band Multiplexer combines the UL and DL RF signals of the supported services in addition to external RF signal future option for connecting to external 2 5 GHz signal source while providing the proper filtering into a single duplexed antenna port Power entry module PEM Local AC or Remote DC power feed model dependent Fan module FAM integrat...

Page 14: ...port TEST PORT QMA coupling test port used for UL and DL measurements during system operation 2 5 GHz INPUT PORT N A Future option Min DIN 4 3 10 RF input port for 2 5 GHz external RF source GND One two hole standard barrel grounding lug PEM Power Connector Model dependant AC models AC connector connected to power source using provided AC power cable only DC models two types of terminal block conn...

Page 15: ... and operational Rapid blinking green Identify feature has been enabled via the management GUI Off No power inpout detected STS Steady green Normal operation overall status OK Steady red Indicates generated alarm in unit Blinking red Over temperature alarm active Indicates temperature has exceeded threshold with door open Note Temperature alarm is set as first priority and overrides any other alar...

Page 16: ... specified equipment with the provided grounding bolt Do not use the grounding bolt to connect external devices Follow electro static discharge ESD precautions Use low loss cables to connect the antennas 3 3 Installation Requirements Mounting surface shall be capable of supporting the weight of the equipment In order to avoid electromagnetic interference a proper mounting location must be selected...

Page 17: ...er than direct connections to the branch circuit e g use of power strips 3 3 1 2 Rack Installation Guidelines To maintain a low center of gravity ensure that heavier equipment is installed near the bottom of the rack and load the rack from the bottom to the top Verify that the rack height can support the unit to be installed MRU rack height 6U where you may also want to consider future installatio...

Page 18: ...t type Cable length determined by the system installation plan When calculating the cable length take into account excess cable slack so as not to limit the insertion paths 3 5 2 RF Rules Use coax RG 223 50 ohm male to male N type to QMA for RF connections from the RIMs to the BTS RBS and to the MRU When using the Corning remote unit in an environment in which other indoor coverage systems are ins...

Page 19: ...th Coax Loss 900 MHz Connector Loss Total Loss 70 1 5 1 5 3 80 1 7 1 5 3 2 90 1 9 1 5 3 4 100 2 1 1 5 3 6 110 2 3 1 5 3 8 120 2 5 1 5 4 130 2 7 1 5 4 2 140 2 9 1 5 4 4 150 3 1 1 5 4 6 160 3 3 1 5 4 8 170 3 5 1 5 5 180 3 7 1 5 5 2 190 3 9 1 5 5 4 200 4 1 1 5 5 6 ...

Page 20: ... coupler separately ordered from Corning P N AK 1COUPLER NM NF or the equivalent Broadband frequency 300 3000 MHz 20 dB coupling SMA coupling port Max VSWR Return Loss 12 dB Max Insertion Loss dB 0 2 Number of antennas that can be connected with cables splitters it is not recommended to connect more than one antenna per connector since 1 1 connectivity is reduced with each split Types of couplers ...

Page 21: ...nsmission characteristics of the cable The cable may have to be replaced Use an optical power meter and light source for checking the fiber optic cables Make sure the environment is clean while connecting splicing fiber optic cables All fiber optic connectors should be cleaned prior to connecting to the system Fiber connector protective caps should be installed on all non terminated fibers and rem...

Page 22: ...sted items are missing contact your Corning representative 3 Check for signs of external damage If there is any damage call your Corning representative Kit Item Description Quantity MRU Mid power remote unit Note See Appendix B Ordering Information for MRU part numbers 1 Hosted Modules pre installed Service specific Power Amplifier Modules PAM pre installed according to ordered configuration 1 5 F...

Page 23: ...e following MRU chassis requires 6 U rack height availability Rack nuts and screws not provided To install MRU in rack 1 Determine the location of the MRU in the rack while considering additional units e g ICU Power Supply 2 Referring to Figure 4 1 secure the units rack ears to the rack frame as follows Insert two screws half way into the rack frame one on each side Position the bottom half slots ...

Page 24: ...ing the installation to the surface type 4 2 2 1 Unpacking and Inspection Unpack and inspect the carton as follows 1 Open the shipping carton and carefully unpack each unit from the protective packing material 2 Verify that all the items listed in Table 4 2 are included in the wall mount bracket package If any of the listed items are missing contact your Corning representative 3 Check for signs of...

Page 25: ...U 2 Select location and mark and drill appropriate holes in wall IMPORTANT MRU is installed belly to the wall with door opening rightward If installed near a right facing wall make sure that there is at least 16 inches of clearance to open the door to the right and to successfully remove and replace all modules Figure 4 3 Wall Mount Bracket Dimensions ...

Page 26: ...Installation CMA XXX AEN Page 26 Draft 3 Insert anchors in wall hang unit and tighten to secure Figure 4 4 Mounting MRU on Wall ...

Page 27: ...sure for single MRU installations 1 MRU Mid Power remote unit 1 External Alarms Cable AK MRU DCA CBL DB9 male open wire cable for external alarm connections 1 Table 4 3 Items Required for Outdoor Installation Additional required items not provided Standard electrician tools including ratchet wrench with extension bar and 8 mm socket for tightening self drilling screws securing MRU chassis to cabin...

Page 28: ... and reassemble according to position shown in Figure 4 5 Figure 4 5 Required Position of MRU Rack Ears 2 Referring to Error Reference source not found for relevant knockouts use appropriate knockout tools to punch out knockouts for routing connection cables Figure 4 6 Required Knockouts Positions ...

Page 29: ...arefully lay cabinet on backside so door faces upwards and open door ATTENTION Make sure that the door hatch lock into the door rail See Figure 4 7 Note Push hatch inwards towards the door to release and close the cabinet Figure 4 7 Opening Cabinet Door and Locking in Place ...

Page 30: ...due to narrow space between chassis and cabinet rails 3 Position the bottom half slots of the MRU rack ears onto the protruding screws and tighten the screws using a ratchet wrench Refer to Figure 4 9 Figure 4 9 Securing MRU to Cabinet Rails 4 Insert at least two additional screws into each of the cabinet rails to safely secure MRU and tighten 5 Optional Insert the appropriate conduits refer to se...

Page 31: ...ufacturers installation guide for instructions on cabinet grounding Using one of the grounding cables provided with the cabinet ground the MRU chassis via the two hole standard barrel grounding lug located on the front panel to one of the cabinet grounding bolts Refer to Figure 4 10 Figure 4 10 Grounding MRU to Cabinet ...

Page 32: ...nections route DC power cable with open wires without connector and then wire according to instructions in section 4 7 2 9 Perform external alarm connections between MRU and cabinet A Connect the external alarms cable provided with the MRU to the chassis s DB 9 External Alarms connector The connector provides indications for door opening heat exchanger HEX and one additional input for future use R...

Page 33: ...tion Color Description Red 48 V_COMMON Green 48 V_EXIST INDICATION Brown 48 V_DOOR ALARM Black 48 V_HEX ALARM White 48 V_FUTURE ALARM Table 4 6 External Alarms Cable Wiring Description Refer to Table 4 7 for wiring description of MRU External Alarms connector and to Error Reference source not found for examples of the upper and lower bock cabinet wiring connections External Alarms Connector Pin No...

Page 34: ...randed copper or 12 AWG to 10 AWG solid wire conductors Note The length of the grounding wire depends on the proximity of the switch to proper grounding facilities Phillips head screwdriver Crimping tool to crimp the grounding wire to the grounding lug Wire stripping tool to remove the insulation from the grounding wire Connecting system ground 1 Use a wire stripping tool to remove approximately 0...

Page 35: ...ounding Lug Connection 4 4 Fiber Connections To connect optic fiber 1 Remove the LC APC connector plugs 2 Using Corning SMF 28 fiber or compatible connect the MRU LC APC fiber connector towards the ICU See Figure 4 15 Figure 4 15 Fiber Connections Towards ICU ...

Page 36: ...ne 4 3 10 Type RF port used for connecting to a 2 5 GHz external RF source e g picocell 4 6 External Alarm Connections A DB 9 female pin External Alarms connector located on optical module below RJ45 ports provides support for up to three external dry contact alarm connections from external sources incoming outputs See Figure 4 17 Figure 4 17 MRU External Alarms Connector and Cable The connector p...

Page 37: ...alarm 7 HEX heat exchange alarm 8 Future alarm 9 Exist indication indicates existing connection of alarm cable Table 4 8 MRU External Alarm Connector Pin Out Description Figure 4 18 MRU External Alarms Connector Pin Out Refer to Table 4 9 and Figure 4 19 for dry contact alarms cable wiring description Color Description Red 48 V_COMMON Green N48 V_EXIST INDICATION Brown N48 V_DOOR ALARM Black N48 V...

Page 38: ... 4 7 2 DC Models DC models include two types of terminal block connectors CLASS 2 default two eight pin terminal block connectors for remote feed see section 4 7 2 1 CLASS 1 one two pin terminal block for local plant feed To use CLASS1 user must change default connector mode from CLASS 2 to CLASS 1 see section 4 7 2 2 4 7 2 1 CLASS2 Connector Remote Feed Note the following The CLASS2 DC connector ...

Page 39: ...ering from the end of the DC wire pairs 3 Open the terminal block screw above the negative feed position and then insert the exposed black wire negative feed into the terminal block Note Ensure that no exposed portion of the DC wires extends from the terminal block plug 4 Torque the terminal block captive screw above the installed wire lead using a ratcheting torque screwdriver Recommended torque ...

Page 40: ...S2 mode position to CLASS1 DC CLASS1 power specs Power input 48 VDC 40 60VDC Max current consumption 9 A To perform CLASS1 DC connector wiring 1 Loosen PEM captive screws and pull out module from chassis See Figure 4 22 Figure 4 22 Extracting PEM from Chassis 2 Move DC bridge from CLASS2 position to CLASS1 to set DC input source type to CLASS1 connector Refer to Figure 4 23 Figure 4 23 Setting CLA...

Page 41: ...that no exposed portion of the DC wires extends from the terminal block plug 7 Torque the terminal block captive screw above the installed wire lead using a ratcheting torque screwdriver Recommended torque is 0 49N m 8 Repeat the same process as in Step 6 and Step 7 for remaining positive feed exposed red wire CAUTION Secure the wires coming in from the terminal block so that they cannot be distur...

Page 42: ...0 MHz WCS 2300 MHz RF Parameter DL UL DL UL DL UL DL UL DL UL Frequency Range MHz 729 746 746 756 699 716 777 787 862 869 869 894 817 824 824 849 1930 1995 1850 1915 2110 215 5 1710 1755 2350 2360 2305 2315 Max Output Power Per Antenna Port dBm 30 30 33 33 33 Input Power dBm 0 37 0 37 0 37 0 37 0 37 UL Gain Range dB 19 to 15 19 to 15 19 to 15 19 to 15 19 to 15 Input IP3 dBm AGC OFF Typical 5 5 5 5...

Page 43: ...tandards and Approvals Laser Safety FDA CE 21 CFR 1040 10 and 1040 11 except for deviations pursuant to laser notice no 50 and IEC 60825 1 EMC Radio FCC 47 CFR Part 15 22 24 27 Safety UL 60950 IEC 60825 1 2007 IEC 60825 2 2010 CAN CSA C22 2 No 60950 1 03 NEBS GR 63 GR 1089 GR 487 with outdoor enclosure Optical Optical Output Power 9 dBm Max Optical Budget 7 dB 5 dB over any temp and optical variat...

Page 44: ... block Two DC In eight pin Class 2 terminal block connectors one pair for each PAM total of five pairs and one pair for the FAM OPTM one RSV pair One QMA input connector for EXP UL One QMA output connector for EXP DL One DB 9 female external alarm connector for external dry contact alarm connections Power Power Consumption DC Version 330 W maximum AC Version 360W maximum AC Power Input 100 240 VAC...

Page 45: ...ith three PAM modules supporting LTE700 ESMR and PCS MRU 81719 AC MRU AC assembly with three PAM modules supporting ESMR AWS and PCS MRU Stand alone Modules Note Stand alone modules can be ordered for upgrade or maintenance purposes Part Number Description MRU Chassis assembly with FAM Mid Plane Cavity Filter MUX MRU OPTM P Mid power unit optical module supporting IF and listening mode MRU PAM 17 ...

Page 46: ...y trunk cables no conductive pairs MTP connector is standard for other options please contact Customer Care 11 Note 2 Cable lengths Preconnectorized cable can only be ordered in 10 ft increments Non connectorized bulk cabling can only be ordered in 50 ft increments Select kit Note 3 Available for 24 and above fiber cables only K Two strain relief trunk holders see Note 3 N None Corning Optical Com...

Reviews: