Evaporator Temperature Sensor Temperature versus
Resistance
Temperature °F (°C)
Resistance (ohms)
32 (0)
9000
40 (4.4)
7183
50 (10)
5468
60 (15.6)
4209
70 (21.1)
3271
80 (26.7)
2566
Table 10, Evaporator Temperature Sensor
Temperature versus Temperature Resistance
Constant Discharge Temperature
Control
General Information
CDTC systems maintain a set outlet temperature
based on the temperature control switch setting. This
is a closed-loop system. The same CDTC sensor is
used on both the front and auxiliary HVAC units.
CDTC Temperature Sensor Test
When testing the CDTC temperature sensor
(
), the resistance will decrease as the tem-
perature increases, as shown in