34
MYDENS 60
COSMOGAS
ATTENTION !!!
If you smell gas:
A - Do not switch on any electric device, telephone
included or any object that can cause sparks;
B - Immediately open doors and windows causing
a current of air that quickly cleans the gas from
the room;
C - From another room, or from a neighbour’s,
immediately call a professionally qualified
technician or the gas supply company. Call the
Fire Service if the former are not available.
24.- check the supply gas pressure, following the procedure
in chapter 6.6;
25.- open the CO2 adjustment screw completely (see figure
6.14 detail “A”);
26.- control and adjust the CO2, following the procedure in
chapter 6.8;
27.- instead of the label that identified the old state of
adjustment, apply the sticker onto the front casing of the
boiler (see figure 6.6), certifying the appliance’s new state
of adjustment, as follows: apply label “B” if the boiler has
been converted from methane to LPG; apply label “A” if the
boiler has been converted from LPG to methane.
A – Microswitch
B - Switch
Figure 6.5 - Positioning electric bridge
A
B
020002.01.043
ON
OFF
6 - OPERATING
Model
Type
of gas
Setting
parameter
3002
Minimum
gas supply
pressure
(mbar)
Maximum
Gas supply
pressure
(mbar)
Gas nozzle
diameter
(mm)
CO2
Maximum
power
(%)
CO2
Minimum
power
(%)
O2
Maximum
power
(%)
O2
Minimum
power
(%)
60
NAT
gas
54
15
27
10,0
9,0 ±
0,3
8,5 ±
0,2
4,9 ±
0,2
5,8 ±
0,2
LP gas
55
25
45
6,5
10,5 ±
0,3
10,0 ±
0,2
4,8 ±
0,2
5,6 ±
0,2
Figure 6.6 - Labels certifying the new status of adjustment of the boiler
Figure 6.7 - Correspondence table for the parameter
3002
and the operating values