background image

6

7

5-2

 

Installing the Sensor Unit

Lift the snap lock on the sensor cover and pull the cover toward you to open it.

Note the position of the connector and the mounting slot as you push the sensor unit into 

place. 

When the sensor unit is securely in place, close the sensor cover.

CAUTION

●  If the Gas Detector is used without a properly seated sensor unit, the Gas Detector 

will not be air-tight and normal detection may not be possible. Make sure the unit is 

properly seated.

●  Use the sensor stocker model EC-7 (purchased separately) to supply power to 

the sensor unit. A sensor unit that does not have power to it cannot detect gases 

and may cause the sensor trouble indicator to light. A sensor unit installed in the 

Gas Detector is powered even if the Gas Detector is turned OFF, as long as the 

batteries are charged.

●  When a sensor unit is replaced (shipped from the plant), install it in the Gas 

Detector or connect it to the sensor stocker model EC-7 to supply a sufficient 

amount of power to the new unit before turning ON the Gas Detector and using it 

for the first time.

●  This Gas Detector uses XDS-7 sensor units and is not compatible with CDS-7, 

COS-7, CHS-7 or any other sensor units.

●Sensor cover

    Lift the snap lock and open the cover.

●Sensor

●Sensor

    mounting slot

●Connector

6

7

5  Operating Procedure

Inspect the Gas Detector daily before using it. (Refer to page 13.) If the Detector is used without 

first performing the inspection, normal detection may not be possible and leaks may not be 
detected.

CAUTION:

The Gas Detector must be turned ON in a clean-air environment. Otherwise, the 

performance of the Detector may be impaired and normal detection may not be 

possible.

5-1  Inserting Batteries

Lift the snap lock on the battery cover and pull the cover toward you to open it.

Insert the four AA alkaline batteries provided and make sure they are inserted according to 

the polarity indicated in the battery compartment.

Close the battery cover.

WARNING

Replace all four batteries at the same time with fresh, new batteries.

Also make sure that the replacement batteries are all the same brand and type.

CAUTION

Always replace the batteries in the following situations.

 The battery indicator shows a flashing box (

) when the Gas Detector is ON. 

(Refer to LCD display on page 5.)

 Nothing operates when the Gas Detector is ON.

 The battery check LED (red) is glowing very brightly (as bright as � above) when 

the Gas Detector is OFF. (Refer to item � on page 4.)

●Battery

   compartment

●Battery cover

Lift the snap lock and open the cover.

Summary of Contents for XPS-7

Page 1: ...his manual Instruction manual No XPS 7T 10 Semiconductor Plant Gas Detector XPS 7 Instruction Manual Store this Instruction manual in a convenient location and consult it whenever necessary Operate th...

Page 2: ...ing Procedure 6 5 1 Inserting Batteries 6 5 2 Installing the Sensor Unit 7 5 3 Turning the Gas Detector ON 8 5 4 Detection 8 5 5 Ending Detection 8 6 Logger Function 9 7 Replacing the Filter 10 8 Dail...

Page 3: ...ath WARNING Indicates a potentially hazardous situation that if not avoided could re sult in serious injury or death CAUTION Indicates a potentially hazardous situation that if not avoided could re su...

Page 4: ...es FS Alarm setting 1st level 2nd level XDS 7NH NH3 Ammonia 100 ppm 12 ppm 25 ppm XDS 7SH SiH4 Silane 25 ppm 2 5 ppm 5 ppm XDS 7DC SiH2Cl2 Dichlorosilane 25 ppm 2 5 ppm 5 ppm XDS 7AH AsH3 Arsine 250 p...

Page 5: ...to open it and access the key switches Buzzer speaker Gas inlet Sampled gas aspiration inlet 6 dia Attaches to the gas inlet tube Gas outlet Exhaust outlet for sampled gas 6 dia Adapter connector Con...

Page 6: ...ecial command switch Used with the logger function UP DOWN switches Used to set the start time and other logger function settings Key Switches LCD Display Log indicator Lit when the log function is op...

Page 7: ...is attached make sure that it will not pull out Removing Press in the release ring on the coupling and simultaneously pull out the gas inlet tube Attaching Removing Gas Inlet Tube Filter case Contains...

Page 8: ...AA alkaline batteries provided and make sure they are inserted according to the polarity indicated in the battery compartment Close the battery cover WARNING Replace all four batteries at the same tim...

Page 9: ...power to the sensor unit A sensor unit that does not have power to it cannot detect gases and may cause the sensor trouble indicator to light A sensor unit installed in the Gas Detector is powered eve...

Page 10: ...after a power failure 5 4 Detection Place the gas sampling pipe near the target detection area When the unit detects gas the concentration of the detected gas is displayed If the detected gas concentr...

Page 11: ...e log data to a personal computer Press the DOWN switch once in RUN mode LOG will be displayed on the lower right corner of the LCD display and the log start time can be entered Press the SPECIAL COMM...

Page 12: ...re factory adjustments that are not available for user application 7 Replacing the Filter Twist the lter holder with detection probe to open it Use a pair of tweezers to remove the O ring and filter I...

Page 13: ...age 6 The batteries are low Replace the batteries The sensor unit is not installed Install a sensor unit Page 7 Abnormal drop in the ow rate The lter is clogged Replace the lter with a new one Page 10...

Page 14: ...After examination of allegedly defective product return to New Cosmos with freight prepaid should the product fail to conform to this warranty customer s only remedy and New Cosmos s only obligation s...

Page 15: ...2 hours of continuous operation at 20 with alkaline batteries and no alarms Operating temperature range 0 to 40 Dimensions W 62 x H 150 x D 128 mm projected portions excluded Mass Approx 1 3 kg Approv...

Page 16: ...Distributor Manufacturer New Cosmos Electric Co Ltd 2 5 4 Mitsuya naka Yodogawa ku Osaka 532 0036 Japan URL http www newcosmos global com XPS 7 09 T XPS 7T 10 2008 100...

Reviews: