background image

4

B 335 -RTP 82 Eng

 

03.93

We reserve the right to make changes without notice

COSTER

D 33056 r.g.

TECHNICAL DATA

Power supply

220/240 Volt ac

Frequency

50/60 Hz

Power absorbed

4 VA

Voltage-free output contact:
– type

SPDT modulating

– voltage rating

250 Volt

– capacity rating

5(3) Amp

Temperature setting range

5 to 30 

°

C

Fixed proportional band

±

 1

°

C

Time switch power reserve

72 h

Minimum switching interval :
– RTP 825 24-hour

20 min.

– RTP 826 7-day

2 h

Room temperature:
– operation

0 to 45 

°

C

– storage

– 20 to +60 

°

C

Room humidity

G (DIN 40040)

Protection

IP 20

Dimensions

 185 x 90 x 52 mm.

Weight

 0.45 Kg

fig. 6

WIRING DIAGRAMS

General layout

Control actuator

with voltage other

than 220/240 Volt

Connection RTP 82. ./D detectors

B1

6

7

8

t

°

t

°

B2

t

°

t

°

B2a

B1

6

7

8

t

°

B1

6

7

8

t

°

t

°

t

°

t

°

t

°

B2b

1

2

L

0

220/240

Volt

ac

T

3

4

5

Y

Co

1

Cl

3

Op

2

RTP 82

1

2

3

4

5

B1

L

0

220/240

Volt

ac

6

7

t

°

Y

Co

1

Cl

3

Op

2

– Room detector SDA 020
– Room detector SDA 010

B2a
B2b

Y
T

– Valve
– Transformer

– Flow detector SIH 010
– Room detector SDA 010

B1
B2

L
0

– Live
– Neutral

COSTER

CONTROLLI

TEMPERATURA

ENERGIA

COSTER

UNI EN ISO 9002

CISQ/CSQ cert.n

°

9115.COEE

Head Office & Sales
Tel.  +39.02.2722121 (TI)
Tel.  +39.02.45476193 (FW)
Fax  +39.02.2593645

Reg. Off. Central & Southern
Tel. +39.06.5573330
Fax +39.06.5566517

Orders and Shipping
Tel. +39.0364.7732.00/02
Fax +39.0364.770016

E-mail: info@coster.info

20132 Milan
Via San G.B. De La Salle, 4/a

00146 Rome
Viale G. Marconi, 437

25048 Edolo (BS)
Via Gen. Treboldi 190/192

Web: www.coster.info

Summary of Contents for B 335

Page 1: ...ors for large spaces SDA 020 NTC 20 kΩ B2 N 110 MODELS Model Description RTP 825 With 24 hour quartz time switch and room detector incorporated RTP 826 With 7 day quartz time switch and room detector incorporated RTP 825 D With 24 hour quartz time switch and remote room detector RTP 826 D With 7 day quartz time switch and remote room detector B 335 03 93 MODULATING ELECTRONIC ROOM CONTROLLERS FOR ...

Page 2: ...value of the room temperature with the desired Normal and Setback temperatures set by means of the two potentiometers on the facia of the case fig 2 6 and fig 2 7 In the event of a difference RTP 82 produces a modu lating signal with PI control action for the control of the valve Y proportional to the difference itself and to the proportional band 1 C The immersion detector B1 monitors the flow te...

Page 3: ... temperature Two values for desired temperature can be set Normal temperature for periods when the premises are oc cupied with the Sun potentiometer fig 2 6 Setback temperature for periods of non occupation of the premises or for the night period with the Moon potentio meter fig 2 7 The setting range of the desired temperatures can be limited by means of two pins fig 3 5 housed on the base at the ...

Page 4: ...ctuator with voltage other than 220 240 Volt Connection RTP 82 D detectors B1 6 7 8 t t B2 t t B2a B1 6 7 8 t B1 6 7 8 t t t t t B2b 1 2 L 0 220 240 Volt ac T 3 4 5 Y Co 1 Cl 3 Op 2 RTP 82 1 2 3 4 5 B1 L 0 220 240 Volt ac 6 7 t Y Co 1 Cl 3 Op 2 Room detector SDA 020 Room detector SDA 010 B2a B2b Y T Valve Transformer Flow detector SIH 010 Room detector SDA 010 B1 B2 L 0 Live Neutral COSTER CONTROL...

Reviews: