background image

11

B 242 - XTE 602 Eng.  C1

 

 22.11.10 AM   

REV. 02

We reserve the right to make changes witout notice

COSTER

16. ALARMS

The alarms processed by the controller are of three types :

– alarms for the irregular operation of the controller and of the heating zones  controlled 

– alarms for short or open circuits detectors connected

– alarms by external contacts

The alarm status is indicated by the LEDs on the controller facia  and is identified, on the configu-

ration page, by the letter “A” alternating with the number of the alarm concerned.

With C-Bus setup the alarms can be sent to a local PC and  / or to the telemanagement central PC.

16.

1

 Functional alarms   

The functional alarms are triggered in the presence of prolonged differences between actual and 

desired values.

These alarms, with the exception of the real time clock alarm (8), do not affect the normal operation 

of the controller. 

Factory setting : all disabled  except for real time clock alarm (8)

Using + and – keys enable the alarms of interest replacing the dashes with the numbers.

When the number blinks = alarm triggered

The limit values and the delay times for sending the alarms can only be modified by PC.

Type of alarm and causes :

1

 = temperature difference heating  zone 1 flow   (B1)

– enabled with pump M1 in operation

– triggered when actual temperature less than that desired.

3

 = temperature difference ambient  (B3)

– enabled with NORMAL modes and with outside temperature below desired ambient tempe-

rature.

– triggered when actual temperature below or above that desired.

5

 = temperature difference heating  zone 2  flow  2 (B5)

– enabled when pump M2 in operation

6

 = temperature difference ambient  (B6)

– enabled with NORMAL modes and with outside temperature below desired ambient tempe-

rature.

– triggered when actual temperature below or above that desired.

8

 = internal real time clock : cannot be disabled

– triggered when clock assumes meaningless values.

16.

2

 Detector alarms

The detector alarms are triggered in the event of 

open

 or 

short

 detector circuits.

Factory setting : all enabled.

With + and – keys disable the alarms which are not of interest by substituting dashes for the numbers.

Type of alarm and effect :

1

 = flow  1 detector (B1) : valve Y1 stops where it is and pump M1 maintains its status at moment 

of alarm.

2

 = outside  detector (B2) : valves stop where they are and pumps maintain their status at moment 

of alarm. In C-Ring last value continues to be transmitted.

3

 = ambient  1 detector (B3) : with pump M1 On, ambient temp. = desired ambient temp.; with  

pump M1 Off, value of ambient temp. calculated by controller.

4

 = anticondensing  detector (B4) : anticondensing function disabled.

5

 = flow  2 detector (B5) : valve Y2 stops where it is and pump M2 maintains its status at moment 

of alarm.

6

 = ambient  2 detector (B6) : with pump M2 On, ambient temp. = desired ambient temp.; with 

pump M2 Off, value of ambient temp. calculated by controller.

8

 = C-Ring : open electric circuit or fault in one of controllers in ring.

The triggering of the alarm is delayed by one minute .

16.

3

 Alarms or status from external contacts (k) 

Alarms triggered by closure of voltage-free contacts

 k1

 ...

 

k3

 regarding plant components (pumps, 

burners, etc).

The triggering of the alarms is delayed by one minute.

 

Factory setting : all disabled.

With + and – keys enable alarms which are of interest by substituting numbers for dashes.

When number blinks = alarm triggered.

If not used as alarms they can be used as status indicators .

25.

5

 F u n c t i o n a l A l a r m s

 

–        –        –    –        8

25.

6

 D e t e c t or  A l a r m s

 

1    2    3    4    5    6        8   

25.

7

 K  A l a r m s

 

–    –    –    –    –

Summary of Contents for COSDTE602

Page 1: ...adjusting Eco Off Timed programming twentyfive 24Hour programs two 7Day periods Programming with dates twentyfive holiday periods winter season special period Summer plant exercise of valves and pumps Automatic change GMT Summer time Metering of degree days Remote control for modifying current timed programmes Three On Off inputs for signalling status or alarm Alarms for detector short or open cir...

Page 2: ...mmes periods 24 hour programmes 1 25 24 hour events 2 6 7 day programmes 0 2 Holiday periods 0 25 Special period 1 Remote Extension period 0 3 72 h Measurement ranges Flow temperature 0 99 C Outside temperature 30 40 C Ambient temperature 0 30 C Anticondensing temperature 0 99 C Heating Flow temperature radiators 40 70 99 C fan coil 40 80 99 C panels 20 40 50 C minimum limit 1 99 C maximum limit 1...

Page 3: ...on the return pipe to the boiler between the anticondensing pump connection and the boiler itself 9 WIRING Proceed as follows Separate base and cover Mount base on DIN rail and check that securing elements 5 4 hold it firmly in place Carry out wiring according to the diagram and in observance of the relevant regulations in force and using cables of 1 5 mm2 for power and relay control outputs 1 mm2...

Page 4: ... and values entered on display pages of the controller and those of configuration dedicated exclusively to telemanagment see 4 TECHNICAL DATA operational status of plant components pumps auxiliaries in general acquire alarms coming from boiler plant read the measurements of the detectors temperatures outside flow boiler etc 10 4 C Bus electrical connection for local or remote Telemanagement Each c...

Page 5: ...e heat emitters with high outside temperatures intermediate seasons Des i gn Ou t s i de Temp 5 0 c 23 2 24 2 Des i gn F l ow Temp 70 0 c 23 3 24 3 Cu r veOr i g i n TO2 0 F l ow T 20 0 c 23 4 24 4 11 OPERATION XTE 602 is a digital controller with microprocessor for compensated control with or without ambient authority of two heating zones Three wire control of motorised valves and On Off control ...

Page 6: ...r each C difference between measured room tempe rature and the desired toom temperature when the measured room temperature is below the desired room temperature NEGATIVE reduction of the flow temperature for each C difference between the measured room temperature and the desired room temperature when the measured room temperature is higher than the desired room temperature 12 8 Eco Off For each he...

Page 7: ...low calculated flow temperature Boosting pump always On Flow pump always On Delay Off 2 min delay time in switching off to dissipate heat accumulated in plant 12 13 Metering degree days For each zone controlled XTE 602 meters degree days in two ways 20 metering of degree days with reference to conventional ambient temperature of 20 C Amb metering of degree days with reference to the actual ambient...

Page 8: ...imisation Maximum period before start occupancy for first startup of plant when controller uses one of 7 day and or 24 hour programmes available in practice startup after being switched off for a night 13 6 Duration optimisation after holiday Maximum period before start occupancy for first startup of plant after a holiday period 13 7 Boosting Increase in desired ambient temperature and consequentl...

Page 9: ...ACK 1 2 FLOW 1 2 FROSTPROT OFF Fr to day and month of start and end of special period 14 5 Extension period The Extension period overrides all programmes and modes in use causing the heating zones to operate for the time and at the temperature set To activate the Extension period close the switch c1 for heating zone 1 or c2 for heating zone 2 for at least five seconds and then open it At the expir...

Page 10: ...cessary to monitor the operational status of the plant ambient temperature desired by modes in use and actual measured by detectors B3 and B6 If the detectors are not connected in place of Act Amb T appears Cal Amb T flow temperatures desired by modes in use and actual measured by detectors B1 and B5 outside temperatures actual If detector B2 is not connected to controller in place of actual appear...

Page 11: ...abled with NORMAL modes and with outside temperature below desired ambient tempe rature triggered when actual temperature below or above that desired 8 internal real time clock cannot be disabled triggered when clock assumes meaningless values 16 2 Detector alarms The detector alarms are triggered in the event of open or short detector circuits Factory setting all enabled With and keys disable the...

Page 12: ... C Ring testing appears only if configured as PRIMARY or SECONDARY in Ensure that all the other controllers connected in C Ring are correctly powered by 230 V AC or 240 V AC for UK market Slave controllers or configured as SECONDARIES in selected on testing page The PRIMARY controller sends a signal every 5 seconds via C Ring On all the displays appears If the connection is positive OK replaces on...

Page 13: ... r ed Temp SETBACK 2 1 4 0c De s i r ed Temp FROSTPROT 6 0 c De s i r ed Temp FLOW 1 2 0 0c De s i r ed Temp FLOW 2 3 0 0c Remo t e Ex t 2 1 0c f o r hou r s 3 An t i condens NO De s i r ed T 5 0 0c Eco O f f H t g1 NO H t g2 NO Op t imi s H t g 1 On NO O f f NO Op t imi s H t g 2 On NO O f f NO Summ e r P l an t Ex e r c i s e NO Ho l i da yP r og H t g2 FROSTPROT 6 0c Ho l 0 1 H t g NO F r to He...

Page 14: ... 24 hour programmes in 21 2 12 4 H t g 2 2 4HOUR 1 19 3 Choice programme for heating zone 2 7DAY 1 2 24HOUR 1 25 NORMAL 1 5 SETBACK 1 2 FROSTPROT FLOW 1 2 OFF Instead of programme may appear REMOTE NORMAL 2 REMOTE SETBACK REMO TE 2c REMOTE FROSTPROT REMOTE OFF SUMMER HOLIDAY SPECIAL REMOTE EXTENSION 12 9 Mode 2 NORMAL Td2 1 0 c Va r 0 0 c 19 5 Mode in use heating zone 2 Td Mode desired temperature...

Page 15: ...4 15 5 Ou t s i de Temp Ac t ua l 2 0 c 22 5 Actual outside temp measured by B2 or coming via C Ring 15 5 If outside detector B2 not connected value co mes via C Ring the word Actual is replaced by C Ring Des Amb T 20 0 c Ac t Amb T 20 5 c 22 1 Ambient T desired by mode in use heating zone 1 Temp measured by ambient detector B3 15 5 Valve and pump LEDs of heating zone 1 blink Des Amb T 20 0 c Ac t...

Page 16: ...blink F l ow T L imi t s M i n 1 c Ma x 9 9 c Minimum and maximum limits flow temperature 12 5 24 5 Valve and pump LEDs of heating zone 2 blink S t a r t i ne r t i a MANUAL 1 00h c 23 9 Optimum start inertia 13 4 Valve and pump LEDs of heating zone 1 blink MANUAL correction of value manually AUTOMAT correction of value automatically Op t S t a r t Ho l i da y Max Du r a t 1 0 0 0h 23 11 Maximum d...

Page 17: ...f controller Group to which controller assigned 10 4 Func t i ona l A l a rms 8 25 5 Disabling functional alarms Factory setting only 8 enabled cannot be disa bled 16 1 1 Alarm difference temp flow 1 B1 3 Alarm difference temp ambient 1 B3 5 Alarm difference temp flow 2 B5 6 Alarm difference temp ambient 2 B6 8 Alarm internal real time clock De t ec t o r A l a rms 1 2 3 4 5 6 8 25 6 Enabling alar...

Page 18: ...18 B 242 XTE 602 C1 Eng 22 11 10 AM REV 02 We reserve the right to make changes witout notice COSTER ...

Page 19: ...19 B 242 XTE 602 Eng C1 22 11 10 AM REV 02 We reserve the right to make changes witout notice COSTER ...

Page 20: ...Wiring Wiring procedure modified 0 99 2650 COSTER TECNOLOGIE ELETTRONICHE S p A Sede Legale 20132 Milano Via San G B De La Salle 4 a E mail info coster eu Web www coster eu COSTER CONTROLLI TEMPERATURA ENERGIA Head Office Sales Via San G B De La Salle 4 a Tel 39 022722121 20132 Milano Fax 39 022593645 Orders Fax 39 0227221239 Reg Off Central Southern Via S Longanesi 14 Tel 39 065573330 00146 Roma F...

Reviews: