11
A 511 - DTC 628 Eng.
06.12.05 LB
We reserve the right to make changes without notice
16. PROGRAMMES & PERIODS WITH DATES
It is possible to program the boiler control operation according to consumer requirements by means
of:
– 7 24hour programmes
– 2 7day programmes
– 25 holiday periods
– 1 special period
– heating season
16. Assigning programme
• Programme = programme assigned:
– 7 DAY 1-2
= with one of the two 7day program (
M2.
9…15
) ;
– 24 HOUR 1-7
= with one of the seven 24hour programS (
M2.
2…7
) ;
– NORMAL 1…5 xx.x c = with one of the 5 Compensated Normal room temp. (
M1.
1…5
) ;
– SETBACK 1-2 xx.x c = with one of the 2 Compensated Setback room temp. (
M1.
6-7
) ;
– FROSTPROT xx.x c = with one othe two Fixed Point flow temp. (
M1.
8
) ;
– FIXED P 1-2
xx c = with one of 2 boiler temp. Fixed Point (
M1.
9-10
) ;
– OFF
= always Off.
16.
2
24hour programmes
In each 24hour programme you can set a maximum of six event start times assigning to each the
desired mode:
• Number of 24hour programmes (1…7) you wish to use.
• Day xx : prog number. (1…7); • hx : Event : number Event (1…6); • From xx.xx Event : start
time
• XXXXXX = mode assigned to period:
– NORMAL 1…5 xx.x c = with one of the 5 Compensat. normal room temp. (
M1.
1…5
) ;
– SETBACK 1-2 xx.x c = with one of the 2 Compensat. setback room temp.(
M1.
6-7
) ;
– FROSTPROT xx.x c = with the Compensated Frostprot room temp. (
M1.
8
) ;
– FIXED P 1-2
xx c = with one of 2 boiler temp. Fixed Point (
M1.
9-10
) ;
– OFF
= always off
The Event start times must be entered in increasing order.
Unused times must be excluded by pr and – keys at the same time
Unused times (– – –) must not be left between Event times.
16.
3
7 day programmes
In each 7day programme you can assign a programme to each day of the week.
• Number of 7day programmes (0…7) you wish to use
• 7day x: Number of programme 1-2 ; • XXXXXXXXX : day of the week;
• XXXXXXXXXXXXX
= prog. assigned to day of week;
– 24 HOUR 1-7
= with one of the seven 24hour programs
(M2.
2…7
) ;
– NORMAL 1…5
xx.x c = with one of the 5 Compensat. normal room temp. (
M1.
1…5
) ;
– SETBACK 1-2
xx.x c = with one of the 2 Compensat. setback room temp. (
M1.
6-7
) ;
– FROSTPROT
xx.x c = with the Compensated Frostprot room temp. (
M1.
8
) ;
– FIXED P 1-2
xx c = with one of 2 boiler temp. Fixed Point (
M1.
9-10
) ;
– OFF
= always off
M2.
2…7
P 1 E v e n t 1 6 . 0 0
N O R M AL 1 2 0 . 0 C
M2.
1
H o w m a n y 7 d a y
p r o g r a m ? 1
M2.
8
H o w m a n y 7 d a y
p r o g r a m : 0
M2.
9…15
7 d a y 1 M O N D A Y
2 4 H O U R 1
M0.
2
P r o g r a m :
2 4 H O U R 1