background image

15

A 511 - DTC 628  Eng.

 

 06.12.05 LB

We reserve the right to make changes without notice

19. COMMISSIONING 

Testing to be carried out when installation has been completed and the electrical wiring and confi-

guration carried out and tested.

19.

1

 Testing C-Ring 

 

The C-Ring testing page appears only if  PRIMARY is configured.

Ensure that the controllers connected in C-Ring:

– are correctly powered from the mains at  ( 230 V~).

– one controller only is configured as

– all the other  controllers are Slave or configured as    

– all the controllers are selected on the testing page

DTC 628 sends via C-Ring a signal every 5 seconds.  On all appears.  If the connection if satisfactory 

the word “YES” replaces “??” on all the displays.  If on one or more displays “YES” does not appear 

this means that there is a break between the last controller with “YES” and the first with “??”:

Examples of testing a C-Ring with four controllers:

– Cont.1 "YES"  – Cont..2 "YES" – Cont..3 "YES" – Cont. 4 "YES" : Connection OK

– Cont.1 "??" 

– Cont. 2 "YES" – Cont. 3 "YES" – Cont. 4 "YES" : Break between 4 and 1

– Cont.1 "??" 

– Cont..2 "YES" – Cont. 3 "??"  – Cont. 4 "??"  : Break between 2 and 3

– Cont.1 "??" 

– Cont..2 "??"  – Cont. 3 "??"  – Cont. 4 "??"  : Break between 1 and 2

19.

2

 Testing control ouputs

With + and – keys select:

• Output : - BURNER = On-Off control burner 

• Status  : - OFF; - ON.

• Output : - MODULAT = modulating control burner

• Status  : - IDLE; - LOWER; RAISE.

• Output : - VALVE = On-Off control shut-off valve.

• Status  : - OPEN; - CLOSED.

• Output : - PUMP = On-Off control pump.

• Status  : - ON; - OFF.

Check result of each operation.

19.

3

 Testing detector connections

Each individual detector can be tested by reading the temperature indicated by the controller in the 

“MEASUREMENTS” menu and deciding if the value is reasonable. 

 C R i n g : ? ?

 C R i n g   c o n n e c t i o n

 S E C O N D A R Y

 C R i n g   c o n n e c t i o n

 P R I M A R Y

M6.

4

 C R i n g   c o n n e c t i o n

 S E C O N D A R Y

 C R i n g   c o n n e c t i o n

 P R I M A R Y

M7.

1

 C R i n g : ? ?

 

 O u t p u t : B U R N E R 

 S t a t u s : O F F  

M7.

2

 O u t p u t : M O D U L A T 

 S t a t u s : I D L E

 O u t p u t : V A L V E

 S t a t u s : C L O S E D

 O u t p u t : P O M P A

 S t a t u s : O F F

Summary of Contents for DTC 628

Page 1: ...back 1 2 Frost Protection Fixed Point at fixed point Use the desired boiler temperatures Fixed Point 1and Fixed Point 2 Zones variable in relation to temperature requested by controllers of these zones connected in C Ring Control 3 wire modulating burner common increase decrease On Off control of boiler shut off valve On Off control boiler pump or manifold or heating plant Timed programming with se...

Page 2: ...re 30 0 5 0 20 0 C Correction curve origin 20 0 40 0 C Desired programmable room temperatures 5 NORMAL 0 0 30 0 C 2 SETBACK 0 0 30 0 C FROST PROTECTION 0 0 6 0 30 0 C Control boiler temperature at Fixed Point 2 desired FIXED POINT temperatures 0 0 99 0 C Control temperature boiler zones Increase boiler temp over that of zones 0 0 5 0 50 0 C Boiler setting data Burner modulation time 30 75 3 600 s ...

Page 3: ...ts see data sheets T 021 and T 022 Apply power 230 V and check its presence across terminals L and N Remove power replace cover on base terminal block and secure it with the four screws supplied 5 3 You are advised not to insert more than two cables in a single terminal of the controller and if necessary to use an external junction box 9 SITING CONTROLLER AND DETECTORS 9 1 Controller The controlle...

Page 4: ...the zone controllers used by the DTC 628 con trollers to regulate the temperature of the boilers Only one of the controllers connected in C Ring can be configured as PRIMARY 10 1 Not connected in C Ring DTC 628 can determine the temp of the boiler by using own programming remote control A to modify program in use 10 2 Connected in C Ring with other Heating DHW circuit controllers DTC 628 can be PRI...

Page 5: ...the same time 11 3 Sending alarms Send alarms NO alarms not sent YES alarms transmitted to central PC PassWTeleman NO password not enabled YES password enabled M6 3 Add r e s s Gr oup M6 2 Send A l a rms NO Pas sWTe l eman NO 11 C BUS COMMUNICATION FOR TELEMANAGEMENT for detailed information see data sheet T 021 Via the C Bus output DTC 618 can be Telemanaged two way data communication with one or...

Page 6: ... o l COMPENS F I XED P M6 1 Compensated control in the timed programming use the room temp NORMAL 1 5 SETBACK 1 2 FROSPROT To ensure the necessary temp for the storage of DHW use the CDB 301 A remote control operated 5 M by the On switch of the storage tank M1 with FIXED POINT 1 temp Control A Fixed Point in the timed programming use the boiler temp FIXED POINT 1 2 Type o f con t r o l ZONES M6 1 ...

Page 7: ... 1 On Off control burner E 3 Modulating control burner F Boiler thermostats M Boiler recycle pump Y Boiler shut off valve Yfc Valve end of run No 1 n Zone controllers Type o f con t r o l ZONES M6 1 You can use different temperature increases for each boiler M1 12 so as to differentiate the load between them By using CDB 301 A remote control for each boiler you can interlock their operation to ext...

Page 8: ...ensated controllers and has to maintain a basic compensated temp that will satisfy the demand of the controllers see Example Plants 12 2 and 12 3 For Compensated temperature control use Room temp NORMAL 1 5 set in M1 1 5 Room temp SETBACK 1 2 set in M1 6 7 Room temp FROSTPROT set in M1 8 The control calculates the desired flow temperature Tf in relation to the outside temperature to measured by det...

Page 9: ... of the two 7day programmes M2 9 15 24 HOUR1 7 with one of the seven 24hour programmes M2 2 7 NORMAL 1 5 xx x c with one of the 5 Compensated Normal room temp M1 1 5 SETBACK 1 2 xx x c with one of 2 Compensated Setback room temp M1 6 7 FROSTPROT xx x c with Compensated Frostprot room temp M1 8 FIXED POINT 1 2 XX C with one of the 2 temp boiler Fixed Point M1 9 10 OFF always Off When in place of pr...

Page 10: ... off burner to avoid overheating of boiler because of residual heat in the combustion chamber 15 3 Control pump for recycle boiler manifold or heating plant M The SPDT switch 8 9 10 can control the boiler recycle pump the manifold pump with several boilers use the switches of the various DTC 628 connected together in parallel the heating plant pump Examples plants12 1 Pump Summer NO pump not used ...

Page 11: ...gned to period NORMAL 1 5 xx x c with one of the 5 Compensat normal room temp M1 1 5 SETBACK 1 2 xx x c with one of the 2 Compensat setback room temp M1 6 7 FROSTPROT xx x c with the Compensated Frostprot room temp M1 8 FIXED P 1 2 xx c with one of 2 boiler temp Fixed Point M1 9 10 OFF always off The Event start times must be entered in increasing order Unused times must be excluded by pressing an...

Page 12: ...tamme is set to meet special requirements and which temporarily replaces the programme set in M0 2 Special programme 7 DAY 1 2 with one of the 2 7day programmes M2 9 15 24 HOUR 1 7 with one of the 7 24hour programmes M2 2 7 NORMAL 1 5 xx x c with one of the 5 Compens normal room temp M1 1 5 SETBACK 1 2 xx x c with one of the 2 Compens setback room temp M1 6 7 FROSTPROT xx x c with the Compensated ...

Page 13: ...values measured by the detectors and the data that serves to monitor the operation of the plant If the detectors are not connected or are damaged will appear Actual outside temperature Boiler temperature desired by current mode and actual measured by B4 detector temperature boiler flue gases measured by detector B7 Maximum temperature flue gases measured by B7 detector after last re set To cancel th...

Page 14: ... maximum limit 7 maximum flue gases temperature B7 transmitted when actual temperature higher than maximum set on Telemanagement PC 8 internal timer fault cannot be disabled transmitted when timer assumes meaningless values 18 2 Detector alarms The detector alarms are triggered in the event of short or open circuits to the detectors connected The effect is delayed by a minute and takes place only i...

Page 15: ...a C Ring with four controllers Cont 1 YES Cont 2 YES Cont 3 YES Cont 4 YES Connection OK Cont 1 Cont 2 YES Cont 3 YES Cont 4 YES Break between 4 and 1 Cont 1 Cont 2 YES Cont 3 Cont 4 Break between 2 and 3 Cont 1 Cont 2 Cont 3 Cont 4 Break between 1 and 2 19 2 Testing control ouputs With and keys select Output BURNER On Off control burner Status OFF ON Output MODULAT modulating control burner Statu...

Page 16: ...ST Fr t o Ou t s i de t emp Ac t ua l 2 0c De s i gn ou t s i de t emp 5 0 c On O f f d i f f e r en t bu r ne r 5 0 c Bu r ne rModu l a t i on t ime 7 5 s Ou t pu t MODULAT S t a t us I DLE De sBo i l e r T 6 0 0c Ac t Bo i l e r T 5 8 0c Cho i c e Menu MEASUREM EN TS M3 Bo i l e r v a l v e De l a y O f f NO Pump De l a y O f f 3 0mi n Keys for scrolling the display pages and positioning the cur...

Page 17: ... 4 16 2 3 To be used in timed events programs Des i r ed r oom T NORMAL 2 20 5 c M1 2 Value of desired room temp NORMAL 2 14 4 16 2 3 To be used in timed events programs Des i r ed r oom T NORMAL 3 21 0 c M1 3 Value of desired room temp NORMAL 3 14 4 16 2 3 To be used in timed events programs Des i r ed r oom T NORMAL 4 19 5 c M1 4 Value of desired room temp NORMAL 4 14 4 16 2 3 To be used in time...

Page 18: ... 6 0 0 NORMAL 1 20 0 c P1 Even t 6 2 2 0 0 OFF M2 2 M2 7 Day xx number of 24hour prog 1 7 hx number of Event 1 6 From xx xx event start time Choice of mode to assign to period NORMAL 1 5 xx x c set in M1 1 5 SETBACK 1 2 xx x c set in M1 6 7 FROSTPROT xx x c set in M1 8 FIXED P 1 2 xx c set in M1 9 10 OFF boiler off Other sets of 6 pages according no in M2 1 Max 6 events To cancel an unused event p...

Page 19: ...ign outside temp for compensated control 14 1 M4 3 Value of design outside temp for compensated control 14 1 De s i gn f l ow t emp 70 0 c Cu r veOr i g i n TO2 0 FLOW T 2 0 0 c M4 4 Correction of heating curve origin 14 1 M5 SETTING BURNER Ref Display Description Notes Sect Bu r ne rModu l a t i on t ime 75 s M5 1 Time required by modulating control to go from minimum to maximum power 15 1 Only i...

Page 20: ...overtemperature B7 8 fault internal timer CR i ng conne c t i on NO M6 4 Definition of C Ring connection NO without C Ring connection PRIMARY controller pilots C Ring connection Only one of devices connected in C Ring can be PRIMARY SECONDARY 10 DTC 628 controllers cannot receive via C Ring the desired temp from the plant controllers Send a l a rms NO Pas sWTe l eman NO M6 2 Enabling alarms to send...

Reviews: