NOTE:
The value of the voltage set for the “UV Alarm” should be
equal to or higher than the value set for “UVP” or else the
unit will shut-down without any audible warning.
˙
O/P Parameter
Model
110V
230V
97 VAC ~ 123 VAC
194 VAC ~ 246 VAC
Setting value range
Model
110V
230V
47 Hz ~ 63 Hz
47 Hz ~ 63 Hz
Setting value range
Model
12V
24V
48V
10.5 VDC ~ 11.5 VDC
21 VDC ~ 23 VDC
42 VDC ~ 46 VDC
Setting value range
5. UV Alarm : Setting Under Voltage (UV) alarm. When the input
voltage is lower than the set value, the SD-series will sound a
“beep” to remind you that the unit is going to shut-down. In the
meantime, the contact in the internal Dry Contact Relay will
open / close.
Default= 10.5 VDC @ 12 V Model, 21 VDC @ 24 V Model.
42 VDC @ 48 V Model
1. O/P Voltage : Setting the SD-series output voltage on the
inverter operation.
Default= 110 VAC @110 V Model, 230 VAC @ 230 V Model
2. O/P Frequency : Setting the SD-series output frequency on the
inverter operation.
Default= 60 Hz @ 110 V Model, 50 Hz @ 230 V Model.
3. Sync Frequency : If a generator is distorted. The output
waveform (too low frequency) is used as AC source, the allowed
frequency window for the incoming AC power can be enlarged.
9