Model
12V
24V
48V
15 VDC ~ 16 VDC
30 VDC ~ 32 VDC
60 VDC ~ 64 VDC
Setting value range
Model
12V
24V
48V
13 VDC ~ 15 VDC
26 VDC ~ 30 VDC
52 VDC ~ 60 VDC
Setting value range
˙
I/P Parameter
2. OVP Recovery : When the DC input voltage is higher than the OVP
setting, the SD-series shuts-down; once the input voltage falls below
the set OVP value, the SD-series will automatically restart.
Default = 15 VDC @ 12V Model, 30 VDC @ 24V Model.
60 VDC @ 48V Model
Model
12V
24V
48V
10 VDC ~ 11 VDC
20 VDC ~ 22 VDC
40 VDC ~ 44 VDC
Setting value range
Model
12V
24V
48V
11.5 VDC ~ 13.5 VDC
23 VDC ~ 27 VDC
46 VDC ~ 54 VDC
Setting value range
3. UVP Setting : Setting Under Voltage Protection (UVP) and
Shut-down on the inverter operation.
Default= 10 VDC@ 12V Model, 20 VDC @ 24V Model.
40VDC @ 48V Model
4. UVP Recovery : When the DC input voltage is below the set UVP
value, the SD-series shuts-down; Once the input voltage rises above
the set UVP value, the SD-series will automatically restart.
Default= 12.5VDC @ 12V Model, 25 VDC @ 24V Model.
50VDC @ 48V Model
1. OVP Setting : Set the Over Voltage Protection (OVP) and shutdown.
Default = 16 VDC @ 12V Model, 32 VDC @ 24V Model.
64 VDC @ 48V Model
8