Intended use of dehumidifier
The dehumidifier is designed for dehumidifying/conditioning atmospheric air only
– filtered with at
least a G4 filter. Unless specifically stated in the manual or in a separate agreement with Cotes or a
Cotes dealer, this dehumidifier must not be used for the following purposes:
•
Conditioning of gases other than atmospheric air at ambient pressure
•
Conditioning air contaminated with any chemical or other aggressive/corrosive elements
including salt (sodium chloride)
•
Conditioning explosive or flammable air
– including using the dehumidifier in ATEX-
classified zones.
The unit is intended for use in residential, commercial and industrial environments.
Operating conditions
– standard models (E)
For the process and regeneration air inlet, the following operating conditions must be respected:
Relative humidity
0
–100%
Temperature
0
–40°C
Pressure
A
mbient ± 100 Pa
It is only possible to deviate from these ranges if such deviations were specifically mentioned when
the order was placed, and special considerations have been incorporated into the unit in order to deal
with this.
Operating conditions
– Cold store models (C)
For the process and regeneration air inlet, the following operating conditions must be respected:
Relative humidity
0
–100%
Temperature process
-25 -
0°C (can be used up to 40 C)
Temperature regeneration
-25 -
40°C
Pressure
Ambient ± 100 Pa
It is only possible to deviate from these ranges if such deviations were specifically mentioned when
the order was placed, and special considerations have been incorporated into the unit in order to deal
with this.
NOTE