Fans
All units in the C30 range of adsorption dehumidifiers are fitted with two fans as standard.
Cotes adsorption dehumidifiers are always configured with a certain amount of “external pressure” to
make sure that ducting does not cause a reduction in the amount of air.
For details about the fans fitted to this particular Cotes dehumidifier, see page 20.
Filters
All models of Cotes adsorption dehumidifiers are fitted with filters to remove undesirable particles or
other pollutants from the incoming process and regeneration air.
Filters of the G4 class are fitted to Cotes C30 units as standard in order to filter the incoming process
and regeneration air.
For details about the filters fitted to this particular Cotes dehumidifier, see page 20 .
Heating units
Cotes C30 dehumidifiers are fitted with electrical heating units of the PTC-type, in order to control the
temperature of the regeneration air entering the unit.
For details about heating units fitted to this particular Cotes dehumidifier, see page 20 .
Heat recovery unit (HR module)
Cotes adsorption dehumidifiers can be fitted with a heat exchanger to make sure that part of the
thermal energy from the regeneration air leaving the unit is extracted, and reused for preheating the
incoming regeneration air. The heat exchanger is placed in an external box equipped with inlets and
outlets for the incoming and outgoing regeneration air.
The heat recovery unit can save as much as 20
–25% on energy consumption, but you have to install
the appropriate ducting and damper for outgoing regeneration air.
For details about the heat recovery unit fitted to this particular Cotes dehumidifier, please contact
your Cotes dealer, or Cotes.
Water condensation unit (LK module)
Cotes adsorption dehumidifiers can be fitted with water condensation units in order to condense
some of the water from the regeneration air leaving the dehumidifier. This is beneficial when a
regeneration air outlet is not a good idea or cannot be fitted.
When a water condensation unit is installed, the regeneration air forms a closed circuit, using
ambient air passing through heat exchangers to cool the regeneration air to below condensation
temperature.
For details about the water condensation unit fitted to this particular Cotes dehumidifier, please
contact your Cotes dealer, or Cotes.