COTES C30
OPERATING AND SERVICE HANDBOOK
page 35/48
Replacing electric heater
The electric heater is mounted under the regeneration air filter box of the dehumidifier.
To replace that unit, disconnect the wiring, unscrew the protection plate and unscrew regeneration
heater box. You can then withdraw the heater from the heater box.
Replacing rotor and shaft
The following is standard procedure for replacing the rotor.
•
Open door at the front of the cabinet
•
Remove the drive belt from the pulley
•
Remove the screws for the rotor shaft
•
Remove the screws for the lower divider and spacers in-between the dividers
Carefully slide out the rotor (including rotor shaft) before the rotor shaft can be dismounted at the
front.