HOW TO INSTALL A CONDENSATION UNIT OR HEAT RECOVERY UNIT
Removing the packaging
Cotes condensation units (LK module) and heat recovery units (HR module) are delivered in a
cardboard box. Please dispose the packaging responsible, and recycle it if possible.
Handling
Cotes condensation units and heat recovery units are built to be very robust, so there is no need for
special handling, apart from normal sensible care and attention.
Note that the weight of the condensation unit is 35 kg and the weight of the heat recovery module is
21
kg. We recommend that you use a forklift to move such units around and to place them in position.
Where to mount the condensation or heat recovery unit
The condensation and heat recovery units are designed for indoor installation mounted directly onto
the Cotes adsorption dehumidifier on the right side connecting the units to the regeneration air flow.
Note that both units cannot be mounted on the dehumidifier at the same time. The condensation or
heat recovery unit must be installed 0
–5 mm away from the C30 dehumidifier.
To ensure stable operation of the dehumidifier with condensation or heat recovery unit the
regeneration filter
– found in the dehumidifier – must be removed. No filter is needed for regeneration
circuit when using a condensation unit and for heat recovery unit a filter is found at the inlet in the
bottom.
Place the foam insulation sheet between the dehumidifier and LK module to lower the risk of external
condensation.