ALCOVE INSTALLATION
All freestanding Harvester stove models are approved for alcove installation using double-wall Type L
or Type PL UL listed vent systems. An alcove must not be greater than four feet deep as measured
from the alcove face wall to the alcove back wall. In addition, the alcove must have at least seven feet
of clearance when measured from the floor to the alcove ceiling. In an alcove installation, side
clearances of fourteen inches from the stove to combustibles and rear clearances of six inches from the
stove to combustibles must be maintained as a minimum. Alcove clearances require the use of listed
UL 641 Type L or type PL vent systems. Contact a certified installer or local building inspector to
obtain information on any local code requirements for such installation.
FIGURE 11: ALCOVE CLEARANCES
MODEL A
B
C
D
HARVESTER
3 12
5
42
TABLE 3: ALCOVE CLEARANCES, IN INCHES