32
ver.071217-2.10
iLEARN
System Manual
iLEARN Door Control Menu Screens
(continued)
3.4 Creep Door Speed -
Default = 35%. (35% corresponds to 21Hz). This is the speed the doors
run when in the “Creep Distance” (approximately 3” from FULL OPEN or FULL CLOSE).
3.5 Slowdown Distance -
Default = 8.0”. This is the distance away from FULL OPEN or FULL
CLOSE where the door speed will change from “Fast” to “Slow”, as set by the iLearn.
3.6 Creep Distance -
Default = 3.0”. This is the distance away from FULL OPEN or FULL CLOSE
where the door speed will change from “Slow” to “Creep”, as set by the iLearn.
3.7 Overdrive Time -
Default = 1.0s. This is the amount of time the door motors run after the
doors reach FULL OPEN or FULL CLOSE.
3.8 CMD Stretch
- Default = 0.0 sec. Command Stretch allows for additional Overdrive Time on
the Door Motors when a Push Button command is received and the Hoistway Doors are thought
to be at their respective travel limits (FULL OPEN or FULL CLOSE). CMD Stretch signal is a “one
shot” signal so as to prevent repeated overdrive requests in the event of a stuck push button.
3.9 Motor Parameters
- These are parameters to be adjusted ONLY at the factory. They include
Motor Minimum Frequency, Motor Minimum Amps, Motor Midpoint Frequency, Motor Midpoint
Amps, Motor Maximum Frequency, Motor Maximum Amps, and Ghost Drive. These parameters
are protected by a Passcode - Call COURION for additional information.
3.9.9 GHOST DRIVE -
Setting Ghost Door to the network address of an iDRIVE will cause that
iDRIVE to function as if door motors were connected to it. However, the motor drive circuits
will never be powered. It appears to the sequencing logic as if the iDRIVE reported that it
reached FULL OPEN or FULL CLOSE in 10ms after being commanded to do so. The Ghost
iDRIVE requires the Interlock Zone Contact (ILF or ILR) to be made when the car is at that
landing. EUD and STOP must also be made. OPEN and CLOSE are ignored.
3.9.10 ATC Limit Bypass -
Provides ability to bypass the 1 minute (1 min) minimum Auto Time
Close parameter. Auto Time Close can be set to as low as 0.2 minutes when the Bypass is
enabled.
Gate Parameters
This menu allows Car Gate Parameters to be adjusted to suit the needs
of individual installations.
IMPORTANT - For changes to these Parameters to take effect, the
COURION CANbus Network must by RESTARTED using Restart
System under Diagnostics.
Summary of Contents for iDRIVE
Page 8: ...8 ver 071217 2 10 iLEARN System Manual PA PAE INTERLOCK PO 70 3A...
Page 14: ...14 ver 071217 2 10 iLEARN System Manual iLEARN Door Control...
Page 19: ...19 ver 071217 2 10 iLEARN System Manual...
Page 20: ...20 ver 071217 2 10 iLEARN System Manual...
Page 36: ...36 ver 071217 2 10 iLEARN System Manual iDRIVE VFD Floor Control...
Page 38: ...38 ver 071217 2 10 iLEARN System Manual iDRIVE G Car Top Control...
Page 41: ...41 ver 071217 2 10 iLEARN System Manual...
Page 63: ...63 ver 071217 2 10 iLEARN System Manual Doors Closing Doors Opening...