51
ver.071217-2.10
iLEARN
System Manual
Error
Code #
Error Message
21
RESTART_SYSTEM -
Restart events are not presented at the iLEARN Display as an Error.
Restart Events are only visible in the Event Log.
22
iLEARN_EVENT_STAY_SET -
Auto Stay-Set activated on hoistway doors.
23
OPEN_STALL_EVENT_CHNG
(In Ver 2.09 this Error Code is not logged in the Event History)
-
Error 23
occurs when a new FULL OPEN point is more than 1/2” different from the previous FULL OPEN point at a par-
ticular landing. Generally, this is caused when the Open Door iSENSOR or iSENSOR Magnet is misaligned.
Check the physical condition of the Open iSENSOR and iSENSOR Magnet. Replace if damaged. Check to
insure that the Open iSENSOR Cable is properly wired to the iDRIVE VFD Floor Control.
See “The Hoistway Doors do not operate or only ‘creep’ at one or more openings” under Issues at Ini-
tial Startup or after System Restart above.
24
CLOSE_STALL_EVENT_CHNG
(In Ver 2.09 this Error Code is not logged in the Event History) - Error
24 occurs when a new FULL CLOSE point is more than 1/2” different from the previous FULL CLOSE point at
a particular landing. Generally, this is caused when the Closed Door iSENSOR or iSENSOR Magnet is mis-
aligned.
Check the physical condition of the Closed iSENSOR and iSENSOR Magnet. Replace if damaged. Check to
insure that the Closed iSENSOR Cable is properly wired to the iDRIVE VFD Floor Control.
See “The Hoistway Doors do not operate or only ‘creep’ at one or more openings” under Issues at Ini-
tial Startup or after System Restart above.
25
DRIVE_UNLOCKED
(Added in Ver 1.09) - Error 25 occurs when a Drive is unlocked by using the iLEARN
Door Control command UNLOCK DRIVES after Error 13 has occured.
26
TIMEOUT_ON_OPEN
(Added in Ver 1.09) - Error 26 occurs when specific Hoistway Doors do not reach
FULL OPEN (actual physical stall), or the iLEARN does not receive sufficient information from the Open iSEN-
SOR to indicate FULL OPEN within analloted time.
Hoistway Door Timeouts occur as follows: If after 10s the iSENSOR magnet is not discovered, the doors go
to slow speed. If after another 10s the “creep position” is not found, the doors go to creep speed. If after 30s
total, the FULL OPEN position has not been found then a “TIMEOUT_ON_OPEN” fault is generated. At this
point, the iLEARN Control will reset the stall position of the corresponding iSENSOR. The hoistway doors will
travel at “creep” speed until the iSENSOR magnet is found and a new FULL OPEN position is identified by the
iLEARN System.
Check the physical condition of the Door Panels and tracks. Make sure there are no physical barriers which
prevent the Hoistway Doors from reaching FULL OPEN. Check the physical condition of the OPEN iSENSOR
and iSENSOR Magnet. Replace if damaged.
Summary of Contents for iDRIVE
Page 8: ...8 ver 071217 2 10 iLEARN System Manual PA PAE INTERLOCK PO 70 3A...
Page 14: ...14 ver 071217 2 10 iLEARN System Manual iLEARN Door Control...
Page 19: ...19 ver 071217 2 10 iLEARN System Manual...
Page 20: ...20 ver 071217 2 10 iLEARN System Manual...
Page 36: ...36 ver 071217 2 10 iLEARN System Manual iDRIVE VFD Floor Control...
Page 38: ...38 ver 071217 2 10 iLEARN System Manual iDRIVE G Car Top Control...
Page 41: ...41 ver 071217 2 10 iLEARN System Manual...
Page 63: ...63 ver 071217 2 10 iLEARN System Manual Doors Closing Doors Opening...