INSTALLATION MANUAL
INSTALLATION
45
ELECTRICAL
HOOK-UP
Avoiding the risk of electrocution
CAUTION
•
All electrical work should be done by a qualified
electrician, otherwise the certification and
warranty will be voided. Furthermore, any
modifications to the electrical components will
also void the warranty.
ELECTRICAL DANGER
Failure to comply with these instructions may
result in serious injury or death by electrocution.
Disconnect or turn off and secure all power
supplies before startingany intervention on the
Covana cover.
Always have a licensed electrical contractor
perform any electrical maintenance or repairs on
the Covana cover. The wiring must comply with
all applicable local electrical codes and
regulations.
The Covana operator must be connected to a
circuit that is protected by a dedicated GFCI that
complies with all applicable local electrical codes
and regulations.
Install the Covana cover in such a way that water
drainage is directed away from the electrical
components.
Do not connect any auxiliary components to the
electrical system of the Covana cover unless
they have been approved by Covana.
Replace electrical components with original
components provided or approved by Covana.
Ask your dealer for replacement parts.
ELECTRICAL WARNING
To reduce the risk of electric shock, the green-
colored terminal or the terminal marked “g,” “gr,”
“ground,” “grounding” or with the
⏚
symbol that
is located inside the supply terminal box or
compartment must be connected to the
grounding that is provided in the electric supply
service panel with a continuous copper wire
equivalent in size to the circuit conductors
supplying the equipment.
Two lugs marked “bonding lugs” are provided on
the external surface or on the inside of the supply
terminal box or compartment. To reduce the risk
of electric shock, connect the local common
bonding grid in the area of the Covana cover.
Use terminals with an insulated or bare copper
conductor not smaller than No. 6 AWG (13.30
mm
2
).
ELECTRICAL CAUTION
•
All field-installed metal components, such as
rails, ladders, drains or other similar hardware,
within 10 ft. (3 m) of the hot tub, must be bonded
to the equipment grounding bus with copper
conductors no smaller than No. 6 AWG (13.30
mm
2
).