MR Series 600K
User Manual
35
The wiring groove requirements of MR series UPS is the same, in above figure.
Step 1 Determine and plan the installation position according to the UPS size (as shown in Figure3-8)
and installation clearance requirement (see3.2.3 Installation Space).
Figure3-8 Size of MR 600K.
Step 2 Drill 4 holes (hole diameter is
φ
13) by hammer drill according to the bottom installation hole size (as
shown in Figure3-10, Figure3-11).
If the UPS is installed on U-steel, drill 4 hole (hole diameter is
φ
14) on the U-steel directly, and then
perform Step 4 directly.