MR Series 600K
User Manual
36
Figure3-9 Bottom size of MR 600K (unit: mm)
Step 3 Install expansion bolts. The structure and installation for the expansion bolt is as shown in Figure3-
10.
Figure3-10 Expansion bolt structure and installation
Take whole expansion tube into the hole as standard of expansion bolt installation depth. Expansion
tube should not higher than ground, which is to avoid effect the following cabinet installation.
The outer height of expansion bolts should be within the range of 30-50mm.
Step 4 Move the UPS from wooden bracket to the ground, and align the bottom installation hole at the
expansion bolt, lock the bolts.