MR Series 600K
User Manual
90
Start the inverter by panel ON combination button 1
When the green indicator of all power module slow flicker, long press the panel “ON” combination
button for 3s, the system inverters to output. Check the system running status in the touch screen,
and ensure that the system turns to inverter power supply mode. During testing, ensure that the
UPS three-phase output voltage and frequency is normal through the real-time data in the touch
screen.
Start the inverter by touch screen 2
In main page of touch screen, click
icon, it will enter the ON/OFF page, as shown in
Figure5-2, click
OK
to perform the start operation.
Figure5-2 ON/OFF page
Step 5 After start the inverter, UPS turns to inverter to supply power. User can check the system running status
chart and ensure if the system turns to inverter supply power. During testing, ensure that the UPS three-
phase output voltage and frequency is normal through the real-time data in the touch screen.
Step 6 Close the OUTPUT switch, measure the output voltage, output frequency by multimeter, and ensure the
voltage and frequency normal, and then, the UPS can be put into use.
Step 7 Start the load. Generally, start the large-power device first, and then start the small-power device.
----End
Summary of Contents for MR Series
Page 1: ...Uninterruptible power supply COVER MR 600 kVA User manual ...
Page 2: ......
Page 10: ......
Page 36: ......
Page 38: ...MR Series 600K User Manual 28 3 2 Installation Preparation 3 2 1 Installation Tools Tools ...
Page 56: ......
Page 60: ...MR Series 600K User Manual 58 Figure4 4 Fault protection with no output Figure4 5 Shutdown ...
Page 61: ...MR Series 600K User Manual 59 Figure4 6 Exit parallel system Figure4 7 Bypass output ...
Page 62: ...MR Series 600K User Manual 60 Figure4 8 Battery INV output Figure4 9 Mains INV output ...
Page 89: ...MR Series 600K User Manual 87 Figure4 57 Confirm to power off ...