MR Series 600K
User Manual
92
Step 4 After the touch screen and all LED indicators are off, the UPS is completely shut down.
----End
5.3.4 Switch to Bypass Mode Manually
Before shutting down the inverter, please ensure that the bypass is normal. If bypass abnormal, after
shutting down the inverter manually, the system will be with no output and the power supply for load
will be breaked off.
Shut down the UPS inverter, please see step 2 in
5.3.3 UPS Shutdown
, The system will turn to bypass
to supply power automatically.
When the bypass input voltage or frequency exceeds the setting value, shutting down the inverter will
cause system without output, and the power supply for load will be interrupted.
5.3.5 Switch to Maintenance Bypass Mode From Normal Output
Unless professional person, no one can perform the following operation. Manufacturer does not take
charge of the problem caused by the operation of untrained person.
Step 1 Shut down the inverter. In main page, click
icon, it will enter ON/OFF interface, click
OFF
and then click
OK
icon to shut down the inverter.
The inverter also can be shut down by OFF combination button on the panel, generally, it is not
suggested to operate like this.
Step 2 After switch to bypass and the energy flow on the touch screen shows bypass output, place the
MAINTENANCE switch to ON position.
Step 3 Disconnect the POWER switch
→
external battery breaker
→
BYPASS switch.
Summary of Contents for MR Series
Page 1: ...Uninterruptible power supply COVER MR 600 kVA User manual ...
Page 2: ......
Page 10: ......
Page 36: ......
Page 38: ...MR Series 600K User Manual 28 3 2 Installation Preparation 3 2 1 Installation Tools Tools ...
Page 56: ......
Page 60: ...MR Series 600K User Manual 58 Figure4 4 Fault protection with no output Figure4 5 Shutdown ...
Page 61: ...MR Series 600K User Manual 59 Figure4 6 Exit parallel system Figure4 7 Bypass output ...
Page 62: ...MR Series 600K User Manual 60 Figure4 8 Battery INV output Figure4 9 Mains INV output ...
Page 89: ...MR Series 600K User Manual 87 Figure4 57 Confirm to power off ...