COVER serii NHS – User Manual
COMEX S.A.
16
Table 2-8 Description of the power supply interface outages
Pin
Description
Purpose
J10.1
UTI_FAIL_NC
Relay informing about power failure - normally closed (J10.1 and J10.3). Its opening
means the occurrence of decay and battery operation.
J10.2
UTI_FAIL_NO
Relay informing about power failure - normally open (J10.2 and J10.3). Its closure
means the occurrence of decay and battery operation.
J10.3
GND
Common pin for signals NO/NC.
2.7.8. Port USB, RS-232 and RS-485
The USB, RS-232 and RS-485 ports are used to communicate the power supply with the monitoring
software, and to configure the UPS by the authorized service of the manufacturer.
2.7.9. Smart Slot x2
The UPS is equipped with two slots for additional communication cards, including an SNMP card.
Features:
SNMP MIB for UPS monitoring and management
built-in 10/100 MB Fast Ethernet port
management and configuration via WEB, telnet, SSH or NMS interface
support for TCP / IP, UDP, SNMP (v1 / v2 / v3), Telnet, SNTP, HTTP, HTTPS, SSH, SMTP, FTP,
DynDNS, DNS, BOOTP / DHCP protocols,
easy configuration and updating of the card using Windows, Linux, MacOS X.
sending information about events via SNMP Trap, e-mail, SMS
generating daily event reports and sending them via e-mail
performing a secure shutdown of operating systems while keeping open files
NetAgent9 (BY506 and BY505) - support for an environmental sensor, an external GSM modem