COVER serii NHS – User Manual
COMEX S.A.
37
Submenu
Parametr
Description
Date&Time
Date format setting
There are three possible selection formats
(a) year / month / day, (b) month / day / year,
(c) day / month / year
Time setting
Date and time setting
Language
Current language
Language in current use
Language selection
English or Chinese
COMM.
Device Address
Setting the device address
RS232 Protocol Selection
SNT, ModBus, YD / T or Dwin (for service)
Baudrate
Setting the reading speed for the communication
protocol
Modbus Mode
ASCII or RTU
Modbus parity
Parity setting for Modbus
USER
Output voltage Adjustment
Setting the voltage value
Bypass Voltage Up Limited
To 10%
,
+15%
,
+20%
,
+25%
Bypass Voltage Down Limited
To choose:-10%
,
-15%
,
-20%
,
-30%
,
-40%
Bypass Frequency Limited
To choose
:
+/-1Hz
,
+/-3Hz
,
+/-5Hz
Dust Filter Maintenance Period
Setting the date of polyline filter changes
BATTERY
Battery Number
Setting the amount of batteries (12V
)
Battery Capacity
Setting the capacity of batteries (Ah)
Float Charge Voltage/Cell
Setting the charging voltage in float mode for the
battery cell
(
2V
)
Boost Charge Voltage/Cell
Setting the charging voltage in boost mode for the
battery cell
(
2V
)
EOD(End of charge)
Voltage/Cell,@0.6C Current
Set the battery disconnection voltage when the
battery is discharged 0.6xC
EOD (End of charge)
Voltage/Cell,@0.15C Current
Set the battery disconnection voltage when the
battery is discharged 0.15xC
Charge Current Percent Limit
The percentage setting of the battery charging
system performance
Battery Temperature
Compensate
Setting the temperature correction factor of the
charging voltage
Boost Charge Time Limit
Set the duration of charging in mode boost