COVER serii NHS – User Manual
COMEX S.A.
38
Submenu
Parametr
Description
Auto Boost Period
Auto boost loading duration settings
Auto Maintenance Discharge
Period
Setting the period of automatic battery testing
SERVICE
System Mode
Single ,parallel, Single ECO, parallel ECO,LBS,
parallel LBS
RATE
Configure the rated Parameter
For service
CONFIGURE
Configure the system
For service
The user has access to the settings Date and time, communication protocol and language without
password. Other settings are available after entering the password for level 1 or 2, available only
through the authorized service of the manufacturer.
5.2.1.4. Log
Touch icon
(at the bottom of the panel), the system will switch to the display mode of the Log
window shown below. The event logs window displays all events and alarms that occurred during
operation. Each event defines exactly the date and time of its occurrence and resignation.
2014
2 14
2014
2 14
2014
2 14
2014
2 14
2014
2
2014
2 14
2014
2
2014
2
14
14
14
2014
2 14
2014
2 14
29
Load On UPS-Set
Module-Exit-Set
Byp Freq Over Track-Set
Load On Bypass-Set
Bypass Volt Abnormal-Set
Load On Bypass-Set
No Load-Set
Load On Bypass-Set
Byp Freq Over Track-Set
Module Inserted-Set
0
4
0
0
0
0
0
4
0
4
1
2
3
5
6
7
4
8
9
10
16 26 1
16 24 27
16 22 31
16 21 33
16 21 33
16 19 41
16 18 45
16 18 45
16 18 45
16 26 1
Each event that has occurred is saved in the history (Log) and contains the exact time and date of
occurrence, sequence number, description of the event and is highlighted in the red frame.
Event sequence number (NO.) - defines the number of the event in the reverse order of the time it
occurred. The earliest events have the number 1.
Event description (M # EVENTS) - displays the description of the event, warning or damage. The
number given before the description indicates the location of the event: 0 # - system housing, n # -
where n = 1,2, ... 10 refers to a specific power module. Power modules are counted from the bottom.
Event Time (TIME) - defines the exact date and time of occurrence of an event.
Total Log Items - defines the total number of registered events. The maximum number of events that
can be saved is 895. If this amount is exceeded, the oldest entries are deleted.