COVER serii NHS – User Manual
COMEX S.A.
40
Clearing the history of the use of a pollen filter
– Clicking th icon
allows you to delete the
entire history associated with the use of the filter, exchange dates, etc.
Command keys:
Battery test
– Clicking the icon
allows you to switch the system to battery mode for battery
testing. Before switching on the test, make sure that the bypass is available and the battery capacity is
greater than 25%.
Battery operation
– clicking the icon
allows you to switch the system to battery mode to check
the battery. Before switching on the test, make sure that the bypass is available and the battery capacity
is greater than 25%.
Charging boost
– clicking the icon
allows charging accelerated in boost mode.
Charging float
– clicking the icon
allows you to charge in the normal Float mode.
Interupted test
– clicking the icon
causes the battery test to be interrupted.
5.2.1.6. Scope
Touch icon
(in the lower right part of the panel), the system will switch to the oscilloscope
window display mode shown below.
220.2
220.0
220.1
The oscilloscope function allows the user to view voltage waveforms
and current
on the system
output, and bypass voltage
. Keys
they allow you to enlarge or reduce the image.