 7 

 

When power is applied to the unit, the load will turn on immediately. 

Set the timeout to 10 seconds, vacate the room or remain very still and wait for the load to switch off . 

Check that the load switches on when movement is detected. 

The unit is now ready for programming. 

Power-up test procedure 

What if the load does not turn ON? 

 

Check that the supply to the circuit is good.  

 

If the detection range is smaller than expected, check the diagram on page 2. Rotating the sensor slightly may 
improve the detection range.  

HINT: 

The Walk Test LED function can be used to check that the unit is detecting movement in the required area. 

 

What if the load does not turn OFF? 

 

Ensure that the area is left unoccupied for longer than the Time Out Period. 

 

Ensure that the sensor is not adjacent to circulating air, heaters or lamps. 

Fault finding 

Summary of Contents for EBDSPIR-DD-LV

Page 1: ...set Features Back features Ceiling PIR presence detector DALI DSI 12 24V AC DC EBDSPIR DD LV Product Guide Retaining Spring Retaining Spring Power Input Switched Output Connector Channel 1 Dimmable Co...

Page 2: ...2 Detection diagram Area of lower sensitivity Area of high sensitivity...

Page 3: ...alk Test LED which will flash red when movement is detected Switch Level On Off Occupancy detection can be made dependant on the ambient light level using the Lux On Level and Lux Off Level parameters...

Page 4: ...er is received The device will show multiple flashes of its LED All of the values will be shown against the parameters in the menu The individual parameters may be edited and then saved as a Macro Not...

Page 5: ...upancy Configured to absence detection Press and release up switch to turn on Maintains illuminance Press and release down switch to turn off Press and hold up switch to dim up press and hold down swi...

Page 6: ...dim up press and hold down switch to dim down Turns off after occupancy Channel 1 does not operate with switch Channel mode Set to Switch and dim separate Switch mode Set to 2 position switch separate...

Page 7: ...does not turn ON Check that the supply to the circuit is good If the detection range is smaller than expected check the diagram on page 2 Rotating the sensor slightly may improve the detection range...

Page 8: ...Sets the ballast control protocol to be used by the output channel Sensitivity 9 1 5 9 3 6 8 Sensitivity level for detecting movement 1 low sensitivity 9 high sensitivity Defaults D Returns the unit...

Page 9: ...ernal switch is pressed whether in absence or presence mode if the lights were out because of the lux level they will be immediately turned on again for at least the Lux Time Power Up State On On or O...

Page 10: ...ghts from being turned on by movement Light Level maintained illuminance 600 1 to 998 999 disabled Sets a target light level to be maintained by the lighting system Load Type DALI DSI DALI DALI On Set...

Page 11: ...11 This page intentionally left blank...

Page 12: ...t and should be treated as if mains potential Use mains rated wiring Terminal Capacity 2 5mm2 Temperature 10 C to 35 C Humidity 5 to 95 non condensing Material casing Flame retardant ABS and PC ABS Ty...