Basic programming 

Parameter 
Name 

Default 
Value 

0

 

1

 

2

 

3

 

UHS5 Handset Graphics 

Description 

 

 

Button Activation 

 

 

On / Raise 

 

On 

Raise 

 

 

 

Turn lights on or to raise lights. 

Off / Lower 

 

Off 

Lower 

 

 

 

Turn lights off or to lower lights. 

Walk test 

Off 

On 

Off 

 

 

 

When set to On this causes a red LED to flash on 
the sensor when it detects movement. Use this 
feature to check for adequate sensitivity levels. 

Time Out 

(Time 
adjustment) 

20 mins 

1, 10 & 
20 
minutes 

5, 15 & 
30 
minutes 

10 
seconds 

 

 

Once the detector is turned on, this value sets 
how long the lights will stay on once movement 
has ceased. 

Lux on 
level 

(Switch 
level on) 

2, 5 & 7 

4, 6 & 9   

 

 

Lux level setting to prevent the luminaires being 
switched on if the ambient light level is sufficient 
(adjustable between 1 and 9). The luminaires will 
always be switched on at level 9.  

Light Level 

6 (600) 

 

 

2 (200) 
5 (500) 
7 (700) 

4 (400) 
6 (600) 
9 (999) 

 

Sets a target light level to be maintained by the 
lighting system. 
9 (999) = disabled.  

Lux off 
level 

(Switch 
level off) 

2, 5 & 7 

4, 6 & 9   

 

 

Lux level setting to switch the luminaires off during 
occupancy if the ambient light level goes above 
the setting (adjustable between 1 and 9). Level 9 
will always keep the lights on. This setting can be 
used for “window row switching”. 

Note: the Lux Off Level value must always be 
greater than the Lux On Level value. 

Load Type 

DALI 

 

 

2-DALI 
7-DSI 

2-DALI 
on 

 

Sets the ballast control protocol to be used by the 
output channel. 

Sensitivity 

1, 5 & 9 

3, 6 & 8   

 

 

Sensitivity level for detecting movement. 
1 = low sensitivity 
9 = high sensitivity 

Defaults 

 

 

 

 

 

Returns the unit to the default settings. 

Burn-in 

50 

100 

 

 

Determines how long the output will be at 100% 
so that lamps ‘burn-in’. The ’burn-in’ time is not 
affected by power supply interruptions.  

Presence / 
Absence 

Presence  Presence  Absence   

 

 

Presence mode allows the output to turn on when 
movement is detected and off when movement 
ceases. Absence mode allows the output to turn 
off when movement ceases, but must be manually 
turned on first. 

Shift 

 

 

 

 

 

 

Use this button to select the settings in red and 
blue signified by the ‘Shift 1’ and ‘Shift 2’ LEDs 

Number of Shift key presses 

The functionality of the EBDSPIR-DD-LV is controlled by a number of parameters which can 
be changed or programmed by any of the following devices: 

 

UHS5

 Infrared Handset. See below for programmable functions. 

 

UNLCDHS 

Infrared Handset (with LCD). See user guide for full programming details. 

For most basic programming operations the UHS5 handset can be used and the following procedures 
are based on using this device. 
Point the handset at the Sensor and send the required programming commands to the unit as shown 
below. 
Valid commands will be indicated by a red LED flash. See page 1 for details of other LED responses. 

Note: other functions on the UHS5 which are not shown below are not applicable to this product.

 

 
 
 

SHIFT 1  SHIFT 2 

SHIFT 1  SHIFT 2 

SHIFT 1  SHIFT 2 

SHIFT 1  SHIFT 2 

Summary of Contents for EBDSPIR-DD-LV

Page 1: ...set Features Back features Ceiling PIR presence detector DALI DSI 12 24V AC DC EBDSPIR DD LV Product Guide Retaining Spring Retaining Spring Power Input Switched Output Connector Channel 1 Dimmable Co...

Page 2: ...2 Detection diagram Area of lower sensitivity Area of high sensitivity...

Page 3: ...alk Test LED which will flash red when movement is detected Switch Level On Off Occupancy detection can be made dependant on the ambient light level using the Lux On Level and Lux Off Level parameters...

Page 4: ...er is received The device will show multiple flashes of its LED All of the values will be shown against the parameters in the menu The individual parameters may be edited and then saved as a Macro Not...

Page 5: ...upancy Configured to absence detection Press and release up switch to turn on Maintains illuminance Press and release down switch to turn off Press and hold up switch to dim up press and hold down swi...

Page 6: ...dim up press and hold down switch to dim down Turns off after occupancy Channel 1 does not operate with switch Channel mode Set to Switch and dim separate Switch mode Set to 2 position switch separate...

Page 7: ...does not turn ON Check that the supply to the circuit is good If the detection range is smaller than expected check the diagram on page 2 Rotating the sensor slightly may improve the detection range...

Page 8: ...Sets the ballast control protocol to be used by the output channel Sensitivity 9 1 5 9 3 6 8 Sensitivity level for detecting movement 1 low sensitivity 9 high sensitivity Defaults D Returns the unit...

Page 9: ...ernal switch is pressed whether in absence or presence mode if the lights were out because of the lux level they will be immediately turned on again for at least the Lux Time Power Up State On On or O...

Page 10: ...ghts from being turned on by movement Light Level maintained illuminance 600 1 to 998 999 disabled Sets a target light level to be maintained by the lighting system Load Type DALI DSI DALI DALI On Set...