Advanced programming 

Parameter Name   Default Value   Range / Options   Description  

UHS5  UNLCDHS 

Detector Parameters

 

Walk Test LED 

Off 

On or Off 

When set to On this causes a red LED to flash on the sensor when it detects 

movement. Use this feature to check for adequate sensitivity levels. 

   

Time Out 

(Time adjustment) 

20 minutes 

0-99 minutes 

Once the detector is turned on, this value sets how long the lights will stay on once 

movement has ceased. Select 0 for 10 second delay – use for commissioning only.  

   

Manual Time Out 

10 minutes 

0-99 minutes 

When a manual operation occurs, either via the switch input or the infrared, it 

invokes the timeout period. 

Example 1: a detector in presence mode has a detector timeout of 15 minutes and 

a manual timeout of 3 minutes. When the user leaves the room they press the off 

button. The sensor will revert to automatic after 3 minutes, and then walking back 

in the room will turn the lights on. 

Example 2: using the settings above, the user turns the lights off (say for a 

presentation) but stays in the room. Every time a movement is detected, the 

manual timeout period is re-triggered, but when it doesn’t pick up for the short 

timeout period, the sensor will timeout and revert to automatic. This means the 

lights may turn on inadvertently during the presentation, if the occupants are still 

for the manual timeout period, so adjust the timing carefully. 

   

Sensitivity On 

1 (min) to 9 (max) 

Sensitivity level for detecting movement when the detector is already on.  

*UHS5 

sets Sensitivity On and Off to the same value. 

*

   

Sensitivity Off 

1 (min) to 9 (max) 

Sensitivity level for detecting movement when the detector is off.  

*UHS5 sets 

Sensitivity On and Off to the same value.

 

*

   

Lux time 

0 (disabled) 
1-99 minutes 

If the detector measures the lux level and decides that the output needs switching 
on or off as a consequence, the lux time must elapse first. If at any time during the 
timed delay the lux change reverses then the process is cancelled. Lux Time 
enables absence detection to be implemented with a lux off level set. When the 
button is pressed, the lights will go on, regardless of ambient light level. However, 
if there is sufficient ambient light, they will turn off again after the Lux Time. 

Note 

that whenever the an external switch is pressed, whether in absence or presence 
mode, if the lights were out because of the lux level, they will be immediately 
turned on again for at least the Lux Time.

 

   

Power Up State 

On 

On or Off 

Select No for a 30 second delay on start up. If Yes is selected,   there will be no 

delay on start up and the detector will always  power up detecting. 

   

Disable Detector 

Y or N 

Disables detection, leaving the relay output permanently off with the dimming 

output operational. This mode is used when the unit is for maintained illuminance 

only.  

   

On Delay 

0 minutes 

0-99 minutes 

The On Delay to allows the first channel to switch on after the second channel. A 

typical application for this would be where a detector is controlling lighting and air 

conditioning in an area. When the occupant is detected, the lighting will be turned 

on immediately, whereas the air conditioning may be turned on after 15 minutes. If 

the area is vacated and the detector times out before the delay, then the air 

conditioning would never go on. The delay can be set only for channel 1 using the 

on delay parameter. 

   

Inhibit 

4 seconds 

1 to 999 seconds 

When the detector turns off, a delay is instigated to prevent retriggering. In certain 

circumstances this delay may not be enough. This parameter allows the delay to 

be changed. 

   

Factory default 

Restores factory default settings 

   

Channel Modes

 

Switch only 

Usually used for absence detection - in this mode the dimming channel is not used.  

   

Switch and dim 
together 

Default 

The detector will switch and dim the lighting together.  

   

Switch and dim 
separate 

Provides 2 channel operation – Channel 1 is switched via the relay output, and 

Channel 2 is dimmed / switched via the dimming output.   

   

User Modes

 

Raise  

Increase light level. Reverts when occupancy cycle complete. 

   

Lower 

Decrease light level. Reverts when occupancy cycle complete. 

   

Scene up 

Steps up between 6 pre-defined scenes. 

   

Scene down 

Steps down between 6 pre-defined scenes. 

   

Scene # 

Select the individual scene, between 0 and 6. 

(1 = min. output; 2 = 10%;   3 = 25%; 4 = 50%; 5 = 75%; 6 = 100%) 

   

Override On 

If the lights are off, sending the IR command will turn them on immediately and 

revert to automatic operation using the manual timeout period. 

   

Override Off 

If the lights are on, sending the IR command will turn them off immediately. After 

the manual timeout period (described above), the sensor will revert to automatic. 

   

Cancel 

Cancels the on or off override, returning the detector to normal operation.  

   

Summary of Contents for EBDSPIR-DD-LV

Page 1: ...set Features Back features Ceiling PIR presence detector DALI DSI 12 24V AC DC EBDSPIR DD LV Product Guide Retaining Spring Retaining Spring Power Input Switched Output Connector Channel 1 Dimmable Co...

Page 2: ...2 Detection diagram Area of lower sensitivity Area of high sensitivity...

Page 3: ...alk Test LED which will flash red when movement is detected Switch Level On Off Occupancy detection can be made dependant on the ambient light level using the Lux On Level and Lux Off Level parameters...

Page 4: ...er is received The device will show multiple flashes of its LED All of the values will be shown against the parameters in the menu The individual parameters may be edited and then saved as a Macro Not...

Page 5: ...upancy Configured to absence detection Press and release up switch to turn on Maintains illuminance Press and release down switch to turn off Press and hold up switch to dim up press and hold down swi...

Page 6: ...dim up press and hold down switch to dim down Turns off after occupancy Channel 1 does not operate with switch Channel mode Set to Switch and dim separate Switch mode Set to 2 position switch separate...

Page 7: ...does not turn ON Check that the supply to the circuit is good If the detection range is smaller than expected check the diagram on page 2 Rotating the sensor slightly may improve the detection range...

Page 8: ...Sets the ballast control protocol to be used by the output channel Sensitivity 9 1 5 9 3 6 8 Sensitivity level for detecting movement 1 low sensitivity 9 high sensitivity Defaults D Returns the unit...

Page 9: ...ernal switch is pressed whether in absence or presence mode if the lights were out because of the lux level they will be immediately turned on again for at least the Lux Time Power Up State On On or O...

Page 10: ...ghts from being turned on by movement Light Level maintained illuminance 600 1 to 998 999 disabled Sets a target light level to be maintained by the lighting system Load Type DALI DSI DALI DALI On Set...

Page 11: ...11 This page intentionally left blank...

Page 12: ...t and should be treated as if mains potential Use mains rated wiring Terminal Capacity 2 5mm2 Temperature 10 C to 35 C Humidity 5 to 95 non condensing Material casing Flame retardant ABS and PC ABS Ty...

Reviews: