CPI User Manual for Lithium Ion Online UPS
04/22v.1
Page 18
Interface
Settings
Parameter 2:
Set the acceptable high voltage point and accept-
able low voltage point for Bypass mode by pressing the Down
key or Up key.
HLS:
Bypass high voltage point
For 230 Models:
230-264:
setting the high voltage point in parameter 3 from
230Vac to 264Vac. (Default: 264Vac)
For 120 Models:
120-140:
setting the high voltage point in parameter 3 from
120Vac to 140Vac. (Default: 132Vac)
LLS:
Bypass low voltage point
For 230 Models:
170-220:
setting the low voltage point in parameter 3 from
170Vac to 220Vac. (Default: 170Vac)
For 120 Models:
85-115: setting the low voltage point in parameter 3 from 85Vac
to 115Vac. (Default: 85Vac)
• 07: Bypass voltage range setting
Interface
Settings
Parameter 2:
Set the acceptable high frequency point and ac-
ceptable low frequency point for Bypass mode by pressing the
Down key or Up key.
HLS:
Bypass high frequency point
For 50Hz output frequency models:
51-55Hz:
setting the frequency high loss point from 51Hz to
55HZ(Default: 53.0Hz)
For 60Hz output frequency models:
61-65Hz:
setting the frequency high loss point from 61Hz to
65Hz(Default: 63.0Hz)
LLS:
Bypass low Frequency point
For 50Hz output frequency models:
45-49Hz:
setting the frequency low loss point from 45Hz to
49HZ(Default: 47.0Hz)
For 60Hz output frequency models:
55-59Hz:
setting the frequency low loss point from 55Hz to
59Hz(Default: 57.0Hz)
• 08: Bypass frequency range setting
Interface
Settings
Parameter 2:
Enable or disable programmable outlets.
ENA:
Programmable outlets enable
DIS:
Programmable outlets disable (Default)
• 09 : Programmable outlets enable/disable