CPI User Manual for Lithium Ion Online UPS
04/22v.1
Page 19
Interface
Settings
Parameter 2:
Set up backup time limits for programmable
outlets.
0-999:
setting the backup time limits in minutes from 0-999 for
programmable outlets which connect to non-critical devices on
battery mode. (Default: 999)
• 10 : Programmable outlets setting
Interface
Settings
Parameter 2:
Set up backup time on battery mode for general
outlets.
0-999:
setting the backup time in minutes from 0-999 for
general outlets on battery mode.
DIS:
Disable the autonomy limitation and the backup time will
depend on battery capacity. (Default)
Note:
When setting as “0”, the backup time will be only 10
seconds.
• 11: Autonomy limitation setting
Interface
Settings
Parameter 2:
Set up the charger maximum current.
1/2/4/6/8:
setting the charger maximum current 1/2/4/6/8 in
Ampere. (Default: 4A)
Recharge time VS charging current is as below table.
• 13 : Maximum charger current setting
1500VA 2000VA 3000VA
8A
0.7
1.4
1.1
6A
0.9
1.9
1.4
4A
1.4
20
2.1
2A
2.8
507
4.2
1A
5.6
11.4
8.5
Interface
Settings
Parameter 2:
Set up the EPO function control logic.
AO: Active
Open (Default). When AO is selected as EPO logic,
it will activate EPO function with Pin 1 and Pin 2 in open status.
AC:
Active Close. When AC is selected as EPO logic, it will
activate EPO function with Pin 1 and Pin 2 in close status.
• 16: EPO logic setting