User Manual for Lead Acid Interactive UPS
04/22v.1
Page 23
VD-Series (5000VA-10kVA)
Chatsworth Products (CPI)
Operation in warning status
1. When Fault LED flashes and the buzzer beeps once every second, it means that there are
someproblems for UPS operation. Users can get the fault code from LCD panel. Please check
the trouble shooting table in section 4 for details.
Operation in Fault mode
1. When Fault LED illuminates and the buzzer beeps continuously, it means that there is a fatal
error in the UPS. Users can get the fault code from display panel. Please check the trouble
shooting table in section 4 for details.
2. Please check the loads, wiring, ventilation, utility, battery and so on after the fault occurs.
Don’t try to turn on the UPS again before solving the problems. If the problems can’t be fixed,
please contact the distributor or service people immediately.
3. For emergency case, please cut off the connection from utility, external battery, and output
immediately to avoid more risk or danger.
Adjusting charging current:
1. In bypass mode, press “Test/UP” button and “Mute/Down” button simultaneous for more than
1s to enter the setting menu.
2. Press the “Mute/Down” button until it shows 17 in parameter 1 and press “Enter” button to
adjust the charging current. (Check 3-7 LCD setting for the details.)
Recommended Charge Current setting
Number of battery packs
Quantity (1)
Quantity (2)
Quantity (3)
2U Battery Pack
1
1.5
2
3U Battery Pack
1.5
3
4
3. In parameter 2, you can select the charging current from 1A to 4A by pressing “Test/UP” button
or “Mute/ Down” button. Please confirm the setting by pressing “ON/Enter” button.
4. In parameter 3, it is to adjust the charging current according to the deviation between the actual
charging current and the setting value of the current.
For example, you want to have the charging current in 4A, but in fact, the charging current is measured
only 3.6A. Then, you need to select “+” and change the number to 4 in parameter 3. It means the
setting charging current will be added 0.4A as output charging current. Then, confirm this modification
by pressing “ON/Enter” button. Now, you may press “Test/UP” and “Mute/Down” buttons at the same
time to exit the setting mode.
NOTE 1: Be careful that the maximum charging current should not exceed the battery accepted
charging current.
NOTE 2: All parameter settings will be saved only when UPS shuts down normally with internal or
external battery connection. (Normal UPS shutdown means turning off input breaker in bypass/
no output mode).