background image

6

The following is recommended to maximize 

recovery rates:

A. Use shortest length of 3/8” (inside) diameter refrigeration 

hose on suction side of TR700 series. 

B. If refrigerant is clean, remove all suction side filters, 

screens, etc. 

C. Remove all Schrader type valve cores and any valve 

depressors from hoses and service valves.

D. Use an evacuated DOT recovery tank.

E.  If unit trips off on high pressure, change recovery 

cylinder.

F.  When recovering large amounts of R410A, or if 

recovering under very high ambient temperature, 

we suggest using the CPS brand MT69 Molecular 

Transformator. 

1.  Connect unit as shown in 

Diagram 1

.  

EU Note: 

Recovery tank must be rated for 38 bar.

2.  Open 

Vapor Valve

 on 

Recovery Tank

.

3.  Open 

OUT Valve

 on unit (Do 

NOT Open IN Valve

 

at this time).

4.  Set 

Auto-Manual

 switch to 

MANUAL

.

5.  Push 

Main Power 

Switch “

ON

”.

6.  When unit starts, open 

IN Valve

 on unit to start 

refrigerant flow.

7.  For automatic shut off, set

 Auto-Manual Switch

 to 

AUTO

 

8.  Monitor amount of refrigerant in 

Recovery Tank

.  

WARNING: Do not over fill Recovery Tank

LB

KG

TARE

Refrigerant 

Manifold Set

A/C System

being serviced

IN

IN

OUT

OUT

Optional Cylinder Overfill Sensor Cord

From Outlet Port of Recovery 

Machine to Recovery Cylinder

To Inlet Port of 

Recovery Machine

High Capacity Charging Scale

Optional tank

overfill switch

DOT Recovery

Tank

TR700 Series

Refrigerant 

Recovery 

Machine

Liquid 

Service 

Port

Vapor

Service 

Port

Note: 

The unit is designed to handle large 

amounts of liquid refrigerant.  If during direct 

liquid recovery the compressor begins to make 

a slugging or hammering noise, meter in the 

incoming liquid by closing the IN valve until noise 

subsides.

9.  In 

AUTO

 position, unit will shut off when suction 

pressure falls to 10” hg vac, and 

RED LP Light

 

will energize. In 

MANUAL

 position, unit will run 

continuously.  

•  Monitor

 IN Gauge

•  Set 

Main Switch

 to 

OFF

 once required vacuum 

level is reached. 

10. The following instructions are to reduce the amount 

of residual refrigerants:

•  Open IN and OUT Valves. Select 

AUTO

 on

 Auto-

Manual Switch

.  

•  Disconnect service hose(s) from equipment being 

serviced.

•  Reconnect this hose to the 

Recovery Tank Vapor 

Port

.

•  Set 

Main Switch

 to 

ON

.

•  Slowly open 

Recovery Tank Vapor Port

 so 

IN 

Gauge 

reads 60-70 PSIG. Run for 30 seconds.

•  Close 

IN Valve

. Unit will automatically shut off 

when vacuum is reached. The 

RED LP Light 

will 

energize.

RECOVERY PROCEDURE IS NOW 

COMPLETE. CLOSE ALL VALVES AND 

DISCONNECT HOSES

DIRECT VAPOR OR LIQUID RECOVERY

Diagram 1 - Direct Vapor Or Liquid Recovery

Summary of Contents for BLACKMAX TR700 Series

Page 1: ... BY QUALIFIED PERSONNEL ONLY THIS EQUIPMENT HAS BEEN VERIFIED BY UNDERWRITERS LABORATORIES INC TO MEET EPA S MINIMUM REQUIREMENTS FOR RECOVERY EQUIPMENT INTENDED FOR USE WITH ALL SYSTEMS CONTAINING REFRIGERANTS FROM ARI740 98 CATEGORIES III IV AND V UL CONTROL NUMBER 2HA5 PREMIUM RECOVERY MACHINES Evaluated for performance in accordance with Sec 608 of the Clean Air Act Feb 29 1996 using AHRI 740 ...

Page 2: ... strength stainless steel bourdon tube 0 to 55 bar 800 psi to handle R 410A Removable replaceable cleanable inlet filter Durable double wall high density polyethylene plastic case with integrated carrying handle Powder coated internal aluminum chassis for long life 2 wide adjustable shoulder pad strap 4 skid resistant rubber feet 6 ft 1 82 m detachable power cord US Patents and patents pending Opt...

Page 3: ... disconnecting any hose please use extreme caution WARNING TO REDUCE THE RISK OF FIRE Avoid the use of an extension cord because the extension cord may overheat However if you must use an extension cord the cord shall be 10 awg minimum WARNING Avoid breathing refrigerant vapors and lubricant vapor or mist Breathing high concentration levels may cause heart arrhythmia loss of consciousness or even ...

Page 4: ...15 Amp 13 Amp 15 Amp 10 Amp PowerConsumption 1000 Watts TankOverfillSwitch P P P HighPressureReset Button P Suction Pressure Gauge OuterScale 30 hg to 500 psig 1to20bar 0 1To3 5 MPA 30 hgto500psig 1to20bar InnerScale 76 cm hg to 35 kg cm 100to2000 kPa 76cmhgto35kg cm 100to2000kPa Discharge Pressure Gauge OuterScale 0 to 1000 psig 0to70bar 0To5 5 Mpa 0to1000psig 0to70bar InnerScale 0 to 70 kg cm 0t...

Page 5: ...44mm Diameter Suction and Discharge Gauges Front View Suction and Discharge Shut Off Valves Selectable Manual OR Automatic Shut Off Mode Settings Discharge Port Suction Port with Replaceable Cleanable Filter 4 Skid Resistant Rubber Feet Connection Point For Power Cord Quick Start Guide High Density Polyethylene Case Rear View High Pressure Reset Button TR700E only ...

Page 6: ...sor Cord From Outlet Port of Recovery Machine to Recovery Cylinder To Inlet Port of Recovery Machine High Capacity Charging Scale Optional tank overfill switch DOT Recovery Tank TR700 Series Refrigerant Recovery Machine Liquid Service Port Vapor Service Port Note The unit is designed to handle large amounts of liquid refrigerant If during direct liquid recovery the compressor begins to make a slug...

Page 7: ...en unit starts open IN Valve on unit to start refrigerant flow 7 Monitor weigh scale for increase of weight in the Recovery Tank or view sight glass for liquid refrigerant flow WARNING Do not over fill Recovery Tank 8 Once the weight gain subsides or liquid refrigerant is no longer present in the sight glass close Recovery Tank Vapor Valve Set Main Power Switch to OFF once the IN Gauge pulls in to...

Page 8: ...misused or solely in need of field service maintenance All repaired equipment will carry an independent 90 day warranty This repair policy does not include equipment that is determined to be beyond economical repair WARRANTY DISCLAIMER Use this device to recover only HVAC R refrigerants from sealed HVAC R systems WARRANTY VOIDED IF USED FOR ANY OTHER PURPOSE WARRANTY Figure 2 CPS PRODUCTS INC U S ...

Page 9: ...NAL CALIFICADO ESTE EQUIPO CUENTA CON LA VERIFICACIÓN DE UNDERWRITERS LABORATORIES INC PORQUE CUMPLE CON LOS REQUISITOS MÍNIMOS DE LOS EQUIPOS DE RECUPERACIÓN DISEÑADOS PARA USO CON TODOS LOS SISTEMAS QUE CONTIENEN REFRIGERANTES DE ARI740 98 CATEGORÍAS III IV Y V NÚMERO DE CONTROL UL 2HA5 MÁQUINAS RECUPERADORAS DE PRIMERA CALIDAD Rendimiento evaluado de acuerdo con la Sección 608 de la Ley de Aire...

Page 10: ...xidable super resistente 0 a 55 bar 800 psi para soportar R410A Filtro de entrada removible reemplazable y lavable Estuche de plástico polietileno de alta densidad duradero y de pared doble con manija integrada Chasis interno de aluminio recubierto con polvo para una vida larga Correa hombrera ajustable de 2 de ancho 4 pies antideslizantes de goma Cable de alimentación de 6 pies 1 82 m removible P...

Page 11: ...antes Cuando desconecte alguna manguera sea extremadamente cuidadoso ADVERTENCIA PARA REDUCIR EL RIESGO DE UN INCENDIO Evite usar un cable de extensión ya que dicho cable puede sobrecalentarse Sin embargo si es necesario que use un cable de extensión use uno de 10 awg como mínimo ADVERTENCIA Evite respirar los vapores del refrigerante y el vapor o el vaho del lubricante Respirar niveles altos de c...

Page 12: ... 13Amp 15Amp 10Amp Consumo de Energía 1000 Watts Interruptor de Sobrellenado del Tanque P P P Botón de Reinicio por Alta Presión P Manómetro de Succión Escala Exterior 30 Hg a 500 psig 1 a 20 bar 0 1 a 3 5 MPA 30 Hg a 500 psig 1 a 20 bar Escala Interior 76 cm Hg a 35 kg cm 100 a 2000 kPa 76 cm Hg a 35 kg cm 100 a 2000 kPa Manómetro de Descarga Escala Exterior 0 a 1000 psig 0 a 70 bar 0 a 5 5 Mpa 0...

Page 13: ... de Diámetro Grande 2 1 4 44 mm Vista Frontal Válvulas de Apagado de Succión y Descarga Ajustes de Modo de Apagado Manual o Automático Puerto de Descarga Puerto de Succión con Filtro Reemplazable Lavable 4 Pies Antideslizantes de Goma Punto de Conexión del Cable de Alimentación Guía de Inicio Rápido Estuche de Polietileno de Alta Densidad Vista Trasera Botón de Reinicio por Alta Presión solo para ...

Page 14: ...do del tanque Del puerto de salida de la máquina recuperadora al cilindro de recuperación Hacia el puerto de entrada de la máquina recuperadora Pesa de carga de alta capacidad Interruptor de sobrellenado del tanque Tanque de recuperación DOT Máquina Recuperadora de Refrigerante Serie TR700 Puerto de servicio de líquido Puerto de servicio de vapor IN ENTRADA SALIDA Nota La unidad está diseñada para...

Page 15: ...d arranque abra la Válvula de ENTRADA en la unidad para que comience el flujo de refrigerante 7 Supervise la balanza para ver si hay un aumento de peso en el Tanque de Recuperación o vea la mirilla de nivel para controlar el flujo del refrigerante líquido ADVERTENCIA No llene el Tanque de Recuperación en exceso 8 Cuando la ganancia de peso disminuya o ya no haya refrigerante líquido presente en la...

Page 16: ...tilizados o cuando únicamente sea necesario el servicio de mantenimiento externo Todas las reparaciones del equipo tendrán una garantía independiente de 90 días Esta política de reparación no incluye el equipo que exceda la reparación económica EXENCIÓN DE RESPONSABILIDAD DE LA GARANTÍA Use este dispositivo para recuperar únicamente refrigerantes de equipos de climatización de sistemas sellados de...

Reviews: