6
The following is recommended to maximize
recovery rates:
A. Use shortest length of 3/8” (inside) diameter refrigeration
hose on suction side of TR700 series.
B. If refrigerant is clean, remove all suction side filters,
screens, etc.
C. Remove all Schrader type valve cores and any valve
depressors from hoses and service valves.
D. Use an evacuated DOT recovery tank.
E. If unit trips off on high pressure, change recovery
cylinder.
F. When recovering large amounts of R410A, or if
recovering under very high ambient temperature,
we suggest using the CPS brand MT69 Molecular
Transformator.
1. Connect unit as shown in
Diagram 1
.
EU Note:
Recovery tank must be rated for 38 bar.
2. Open
Vapor Valve
on
Recovery Tank
.
3. Open
OUT Valve
on unit (Do
NOT Open IN Valve
at this time).
4. Set
Auto-Manual
switch to
MANUAL
.
5. Push
Main Power
Switch “
ON
”.
6. When unit starts, open
IN Valve
on unit to start
refrigerant flow.
7. For automatic shut off, set
Auto-Manual Switch
to
AUTO
8. Monitor amount of refrigerant in
Recovery Tank
.
WARNING: Do not over fill Recovery Tank
.
LB
KG
TARE
Refrigerant
Manifold Set
A/C System
being serviced
IN
IN
OUT
OUT
Optional Cylinder Overfill Sensor Cord
From Outlet Port of Recovery
Machine to Recovery Cylinder
To Inlet Port of
Recovery Machine
High Capacity Charging Scale
Optional tank
overfill switch
DOT Recovery
Tank
TR700 Series
Refrigerant
Recovery
Machine
Liquid
Service
Port
Vapor
Service
Port
Note:
The unit is designed to handle large
amounts of liquid refrigerant. If during direct
liquid recovery the compressor begins to make
a slugging or hammering noise, meter in the
incoming liquid by closing the IN valve until noise
subsides.
9. In
AUTO
position, unit will shut off when suction
pressure falls to 10” hg vac, and
RED LP Light
will energize. In
MANUAL
position, unit will run
continuously.
• Monitor
IN Gauge
• Set
Main Switch
to
OFF
once required vacuum
level is reached.
10. The following instructions are to reduce the amount
of residual refrigerants:
• Open IN and OUT Valves. Select
AUTO
on
Auto-
Manual Switch
.
• Disconnect service hose(s) from equipment being
serviced.
• Reconnect this hose to the
Recovery Tank Vapor
Port
.
• Set
Main Switch
to
ON
.
• Slowly open
Recovery Tank Vapor Port
so
IN
Gauge
reads 60-70 PSIG. Run for 30 seconds.
• Close
IN Valve
. Unit will automatically shut off
when vacuum is reached. The
RED LP Light
will
energize.
RECOVERY PROCEDURE IS NOW
COMPLETE. CLOSE ALL VALVES AND
DISCONNECT HOSES
DIRECT VAPOR OR LIQUID RECOVERY
Diagram 1 - Direct Vapor Or Liquid Recovery