has adequate energy. After all conditions are met, the inverter will enter
grid-tied power generation mode. While in grid-tied power generation, the
inverter can detect the power grid at all times, and also keep the photovoltaic
array output in maximum power point tracking (MPPT) mode. In case of any
abnormity, the inverter will enter the protection program immediately. In low
light conditions when power generation is not enough to keep the inverter in
operation, the inverter will enter standby mode. When the voltage of PV array
changes and becomes stable and higher than the required set value, the
inverter will attempt to start grid-tied power generation again.
5.5 Fault shutdown
The inverter will be shut down automatically when the PV power
generation system fails, such as output short circuit, grid overvoltage /
undervoltage, grid overfrequency / underfrequency, high ambient temperature
or internal malfunction of the machine.
The causes of fault can be identified based on the faults listed in Table 5-1.
Proper treatment is recommended before contacting after-sales service. There
are mainly 3 types of faults: alarm, protection and hardware fault.